Troubleshooting – MTS Water Quality Guide User Manual

Page 22

Advertising
background image

Heat Exchanger Care and Water Quality Guide

22

Troubleshooting

Troubleshooting

Symptoms

Corrective Action

HPU won't cool (hydraulic
fluid-to-water models)

Verify the proper water connections:

IN

→IN

OUT

→OUT

Verify that the water temperature vs. flow rate is correct for your
model of HPU (refer to the MTS Hydraulic Power Supply Product
Manual
that came with your system).

Verify that the operation of the water saver valve is correct. Adjust it
if necessary (refer to the instructions in the MTS Hydraulic Power
Supply Product Manual
that came with your system).

Heat exchanger is plugged

Perform a mechanical cleaning

Perform a chemical cleaning as needed

Install a filter in the cooling water inlet line to prevent the buildup of
sediment

Ensure that you are using clean cooling water

Heat exchanger leaks
externally

Inspect the heat exchanger for signs of corrosion

Repair the leak

If the leak occurs at a fitting, it may be loose. Remove the fitting,
inspect it and repair or replace it as necessary. Re-install the fitting,
being careful not to over tighten it.

Heat exchanger leaks
internally

Disassemble the heat exchanger

Conduct a pressure test to determine the location of the leak

Repair the leak if possible, or replace the heat exchanger