PAGE 50 — DCA-400SSK — PARTS AND OPERATION MANUAL (STD)— REV. #3 (09/17/01)

16. Observe the generator's ammeter (Figure 48) and verify

that it reads the anticipated amount of current with
respect to the load. Remember the ammeter will only
display a current reading if the load is in use.

17. The generator will run until manually stopped or an

abnormal condition occurs.

Figure 47. Main and GFCI Circuit Breakers

Figure 48. Ammeter (Load)

A

0

40

60

75

20

15. Turn the MAIN, GFCI and LOAD circuit breakers to their

"ON" position (Figure 47).

DCA-400SSK — GENERATOR START-UP PROCEDURE (KEY SWITCH)

Figure 45. Engine Tachometer

13. The tachometer (Figure 45) will indicate the speed of

the engine when the generator is operating. Under normal
operating conditions this speed should be approximately
1800 RPM’s.

14. Pull the throttle handle to increase the speed of the

engine (Figure 46).

Figure 46. Engine Throttle