Hsk-ex-d standard cable glands, Rohs – Northern Connectors Hummel Cable Glands - Ex-d Standard for Hazardous Areas User Manual

Page 2

Advertising
background image

140

M 12 x 1,5

3 – 6,5

16

18,7

14

1.622.1200.50

1.634.1200.50

M 12 x 1,5

2 – 5

16

18,7

14

1.622.1200.51

1.634.1200.51

M 16 x 1,5

5 – 10

16

22

20

1.622.1600.50

1.634.1600.50

M 16 x 1,5

3 – 7

16

22

20

1.622.1600.51

1.634.1600.51

M 20 x 1,5

10 – 14

16

25

24

1.622.2000.50

1.634.2000.50

M 20 x 1,5

7 – 12

16

25

24

1.622.2000.51

1.634.2000.51

M 25 x 1,5

13 – 18

16

26,5

30

1.622.2500.50

1.634.2500.50

M 25 x 1,5

9 – 16

16

26,5

30

1.622.2500.51

1.634.2500.51

M 32 x 1,5

18 – 25

16

32

40

1.622.3200.50

1.634.3200.50

M 32 x 1,5

14 – 20

16

32

40

1.622.3200.51

1.634.3200.51

M 40 x 1,5

22 – 32

16

38,5

50

1.622.4000.50

1.634.4000.50

M 40 x 1,5

20 – 26

16

38,5

50

1.622.4000.51

1.634.4000.51

NPT 3/8"

5 – 10

16

22

20

1.622.3800.70

1.634.3800.70

NPT 3/8"

3 – 7

16

22

20

1.622.3800.71

1.634.3800.71

NPT 1/2"

10 – 14

20

25

24

1.622.1200.70

1.634.1200.70

NPT 1/2"

7 – 12

20

25

24

1.622.1200.71

1.634.1200.71

NPT 3/4"

13 – 18

20,5

26,5

30

1.622.3400.70

1.634.3400.70

NPT 3/4"

9 – 16

20,5

26,5

30

1.622.3400.71

1.634.3400.71

NPT 1"

18 – 25

25

32

40

1.622.1000.70

NPT 1"

14 – 20

25

32

40

1.622.1000.71

NPT 1 1/4"

22 – 32

26

38,5

50

1.622.5400.70

NPT 1 1/4"

20 – 26

26

38,5

50

1.622.5400.71

NPT 1 1/2"

22 – 32

26,5

38,5

50

1.622.6400.70

NPT 1 1/2"

20 – 26

26,5

38,5

50

1.622.6400.71

M

RoHS

II 2G 1D Ex d IIC

RoHS

II 2G 1D Ex d IIC

HSK-Ex-d standard cable glands

HSK-M-Ex-d / HSK-M-PVDF-Ex-d

Metr.

HSK-M-Ex-d / HSK-M-PVDF-Ex-d

NPT

Protection IP 68 – 10 bar / IP 69K (NEMA 6 – 150 PSIG)

within the specified clamping range

Operating Temperature - 60 °C – 105 °C (- 76 °F – 221 °F) (PA)

- 20 °C – 130 °C (- 4 °F – 266 °F) (PVDF)

O-Ring FPM / FPM

Seal FPM / FPM

Clamping insert Polyamide / PVDF

Material Nickel plated brass

Number Number

AG GL H

HSK-M-Ex-d HSK-M-PVDF-Ex-d

mm mm mm mm

- 60 °C – 105 °C - 20 °C – 130 °C

(- 76 °F – 221 °F) (- 4 °F – 266 °F)

Number Number

AG GL H

HSK-M-Ex-d HSK-M-PVDF-Ex-d

mm mm mm mm

- 60 °C – 105 °C - 20 °C – 130 °C

(- 76 °F – 221 °F) (- 4 °F – 266 °F)

Dimensions and specifications may be changed without prior notice

For the international certificates
please see page 176 or our homepage
www.hummel.com

For the international certificates
please see page 176 or our homepage
www.hummel.com

Protection IP 68 – 10 bar / IP 69K (NEMA 6 – 150 PSIG)

within the specified clamping range

Operating Temperature - 60 °C – 105 °C (- 76 °F – 221 °F) (PA)

- 20 °C – 130 °C (- 4 °F – 266 °F) (PVDF)

O-Ring FPM / FPM

Seal FPM / FPM

Clamping insert Polyamide / PVDF

Material Nickel plated brass

Accessories see page 73 and 143

Accessories see page 73 and 143

Advertising