RKI Instruments GX-8000(H4-0050) User Manual
Page 12

2 Regular Maintenance Mode
GX-8000
- 12 -
<Alarm Setpoint Setting "ALARM-P">
Set the alarm setpoint.
ALARM-P
Press the ENTER switch.
The alarm setpoint setting selection menu is
displayed.
Press the S or T switch to display a target gas for
which the alarm setpoint should be set. Every time
the S or T switch is pressed, the target gas is
changed (in the order of Combustible, O2, H2S, CO,
and ESCAPE).
While a desired target gas is selected, press the
Enter switch to cause the alarm setpoint display
to blink, prompting for input.
Press the S or T switch to change an alarm setpoint
value. Next, press the ENTER switch to enter it.
Continue to set WARNING, ALARM, STEL, and TWA
in this order. (Set the STEL and TWA alarms only for
CO and H
2
S.)
Change the last item and press the ENTER switch.
After the changed settings are confirmed and END is
displayed, the gas monitor automatically returns to
the alarm setpoint setting selection menu (*). Repeat
the same procedure to set other target gases.
When the alarm setpoint setting is completed, press
the S or T switch until ESCAPE is displayed. Press
the ENTER switch to return to the maintenance mode
menu.
Return to ALARM-P.