Sample-Draw Combustible Gas Detection

Overview

This manual describes the Model 1017-04 sample draw combustible gas detector. This
manual also describes how to install, start up, maintain, and calibrate the Model 1017-04.
A parts list at the end of this manual lists replacement parts and accessories.

Specifications

Table 1 lists specifications for the Model 1017-04.

WARNING: When using the Model 1017-04, you must follow the instructions and

warnings in this manual to assure proper and safe operation of the Model
1017-04 and to minimize the risk of personal injury. Be sure to maintain
and periodically calibrate the Model 1017-04 as described in this manual.

Table 1: Specifications

Target Gas

Combustible gas, methane calibration standard

Input Power

24 VDC

Construction (housing)

Cast Aluminum Alloy, Explosion Proof for Class I,
Groups B, C, & D

Dimensions

7.00 in. H x 7.00 in.W x 6.13 in. D

Sampling Method

Sample-draw

Recommended Sample Flow

2.0 SCFH

Detection Range

• 0 - 100% LEL/0 - 10% LEL
• 0 - 100% LEL/0 - 2000 ppm

Response Time

90% in 30 seconds

Accuracy

±5% of reading or ± 2% LEL (whichever is greater)