35-3010RKA-02 Sample-Draw Detector • 1

Overview

This manual describes the 35-3010RKA-02 sample-draw detector. This manual also
describes how to install, start up, maintain, and calibrate the detector. A parts list at the
end of this manual lists replacement parts and accessories for the sample-draw detector.

Specifications

Table 1 lists specifications for the 35-3010RKA-02.

WARNING: When using the 35-3010RKA-02, you must follow the instructions and

warnings in this manual to assure proper and safe operation of the
35-3010RKA-02 and to minimize the risk of personal injury. Be sure to
maintain and periodically calibrate the 35-3010RKA-02 as described in this
manual.

Table 1: Specifications

Target Gases & Detection Ranges

Combustible Gas: 0 - 100% LEL
Oxygen: 0-25% volume
Hydrogen Sulfide (H

2

S): 0 - 100 ppm

Input Power

24 VDC

Current Draw

275 mA

Output Signals

4-20 mA each channel

Construction (housing)

Fiberglass/polyester (NEMA 4X)

Dimensions

15.44 in. H x 12.55 in. W x 8.31 in. D

Weight

14 lbs.

Sampling Method

Sample-draw

Sample Flow

1.2 SCFH (nominal)

Response Time

90% in 30 seconds

Accuracy

Combustible Gas:
± 5% of reading or ± 2% LEL (whichever is greater)
Oxygen:
± 0.5% O

2

Hydrogen Sulfide (H

2

S):

± 5% of reading or ± 2 ppm H

2

S (whichever is greater)