61-1000RKSS Combustible Gas Detector • 11

4.

When the directions call for exposing the detector to zero air, turn the regulator’s on/
off knob counterclockwise to open the regulator.

5.

Allow the gas to flow for one minute before continuing with the directions.

6.

Turn the regulator knob clockwise to close the regulator.

7.

Set the zero reading according to the controller operator’s manual.

8.

Unscrew the regulator from the zero air calibration cylinder.

9.

Leave the sample tubing connected to the regulator and the calibration cup.

Setting the Response Reading

1.

Screw the regulator into the calibration cylinder. Verify that the calibration gas is
representative of the transmitter’s target gas.

2.

Follow the directions in the controller’s operator’s manual for setting the response
reading (span).

3.

When the directions call for exposing the detector to gas, turn the regulator’s on/off
knob counterclockwise to open it.

4.

Allow the gas to flow for one minute before continuing with the directions.

5.

Turn the regulator’s on/off knob clockwise to close it.

6.

Set the response reading according to the controller operator’s manual.

7.

Unscrew the regulator from the cylinder.

Returning to Normal Operation

1.

Unscrew the calibration cup from the detector.

NOTE:

For convenience, leave regulator and calibration cup connected by the sample
tubing.

2.

When the controller display reading falls below the alarm points, return the controller
to normal operation.

NOTE

: If you do not allow the gas reading to decrease below the alarm points, then

unwanted alarms may occur.

3.

Verify that the controller display reading decreases and stabilizes at 0 %LEL.

4.

Store the components of the calibration kit in a safe and convenient place.