Installation, Mounting the combustible gas detector – RKI Instruments 61-0190RK User Manual

Page 7

Advertising
background image

61-1003RK/61-0190RK Combustible Gas Detector • 3

Installation

This section describes procedures to mount the combustible gas detector in the
monitoring environment and wire it to a controller.

Mounting the Combustible Gas Detector

1.

Select a mounting site that is representative of the monitoring environment. Consider
the following when you select the mounting site.

Select a site where the detector is not likely to be bumped or disturbed. Make sure
there is sufficient room to perform start-up, maintenance, and calibration
procedures.

Select a site where the target gas is likely to be found first. For lighter gases,
mount the detector near the ceiling; for heavier gases, mount the detector near the
floor.

Figure 1: Mounting the Combustible Gas Detector

2.

At the mounting site you select, hang or mount the junction box with the detector
facing down (see Figure 1).

Wiring the Combustible Gas Detector to a Controller

WARNING: Always verify that the power to the controller is off before you make

wiring connections.

1.

Turn off the controller.

Junction
Box

Spacer, 3X

IR LEL
Detector

3/4 NPT

Female

3.65

7.1 Max

2.70

0.38