Installation – RKI Instruments 65-2340RK User Manual
Page 9

65-2340RK Toxic Gas Transmitter • 5
Installation
This section describes procedures to mount the toxic gas transmitter in the monitoring
environment and wire the transmitter to a controller.
Mounting the Toxic Gas Transmitter
1.
Select a mounting site that is representative of the monitoring environment. Consider
the following when you select the mounting site.
•
Select a site where the transmitter is not likely to be bumped or disturbed. Make
sure there is sufficient room to perform start-up, maintenance, and calibration
procedures.
•
Select a site where the target gas is likely to be found first.
Figure 3: Mounting the Toxic Gas Transmitter
2.
At the monitoring site you select, hang or mount the junction box with the detector
facing down (see Figure 3).
2.70
.75
0.38
3/4 NPT
Conduit Hub
Rubber
Spacer, 3X
Junction
Box
Toxic
Detector
3.65
9.60 Max