65-2390RK Combustible Gas Transmitter • 1

Overview

This manual describes the 65-2390RK combustible gas transmitter. This manual also
describes how to install, start up, configure, maintain, and calibrate the transmitter when
it is used with a gas monitoring controller. A parts list at the end of this manual lists
replacement parts and accessories for the combustible gas transmitter.

Specifications

Table 1 lists specifications for the combustible gas transmitter.

WARNING: When using the 65-2390RK, you must follow the instructions and warnings

in this manual to assure proper and safe operation of the 65-2390RK and to
minimize the risk of personal injury. Be sure to maintain and periodically
calibrate the 65-2390RK as described in this manual.

Table 1:Specifications

Target/Calibration Gas

65-2390RK-CH4: Methane (CH

4

)

65-2390RK-HC: Propane

Area Classification

Explosionproof for Class I, Groups B, C, and D

Sampling Method

Diffusion

Signal Output

4 to 20 mA

Detection Range

0 to 100% LEL

Response Time

90% in 45 seconds

Accuracy

± 5% of reading or ± 2% of full scale (whichever is greater)