6 • 65-2400RK Combustible Gas Transmitter

Wiring the Combustible Gas Transmitter to a Controller

WARNING: Always verify that the power source is off before you make wiring

connections.

1.

Turn off power to the controller.

2.

Place the controller’s power switch in the OFF position.

3.

Remove the junction box cover.

4.

Verify that the detector leads are wired to the amplifier’s interconnect terminal strip.
If necessary, connect the detector leads to the interconnect terminal strip as shown in
Figure 3.

5.

Guide a three-conductor, shielded cable or three wires in conduit through the top
conduit hub of the junction box.

6.

Connect the three wires to the interconnect terminal strip as follows (see Figure 3).

Connect the positive wire to the

24V

DC

terminal.

Connect the feedback wire to the

4-20

(FB) terminal.

Connect the negative wire to the DC - terminal.

CAUTION:

If shielded cable is used, leave the cable shield’s drain wire insulated and
disconnected at the transmitter. You will connect the opposite end of the cable’s drain
wire at the controller to chassis ground.

7.

Secure the junction box cover to the junction box.

8.

Route the cable or wires leading from the combustible gas transmitter through one of
the conduit hubs at the controller housing.

CAUTION:

Do not route power and transmitter wiring through the same conduit hub. The
power cable may disrupt the transmission of the transmitter signal to the
controller.

9.

Connect the wires to the applicable transmitter terminal strip at the controller as
shown in Figure 3 below.