Overview

This manual describes the 65-2427RK-05 hydrogen sulfide (H

2

S) detector. This manual

also describes how to install, start up, maintain, and calibrate the detector when it is used
with a gas monitoring controller. A parts list at the end of this manual lists replacement
parts and accessories for the H

2

S detector.

Specifications

WARNING: Do not use this product in a manner not specified in this instruction

manual.

Table 1 lists specifications for the H

2

S detector.

NOTE: The following symbol on the detector label is a caution to the user to refer to this

documentation for installation and operation instructions:

WARNING: When using the 65-2427RK-05, you must follow the instructions and

warnings in this manual to assure proper and safe operation of the
65-2427RK-05 and to minimize the risk of personal injury. Be sure to
maintain and periodically calibrate the 65-2427RK-05 as described in this
manual.

Table 1: Specifications

Target Gas

Hydrogen sulfide (H

2

S)

Area Classification

Explosionproof for Class I, Groups B, C, and D

Temperature Code

T6

Installation Category

Installation Category 1. Signal level, special equipment or parts of

equipment, telecommunication, electronic, etc., with smaller

transient overvoltages than Installation Category (Overvoltage

Category) II (ref. IEC 664).

Sampling Method

Diffusion

Detection Range

0 to 100 PPM (parts per million)

H

2

S Detector Signal Output

0.3 mA at 0 ppm H

2

S nominal

2.5 mA at 100 ppm H

2

S nominal

Response Time

90% in 30 seconds

Accuracy

± 5% of reading or ± 2 ppm H

2

S (whichever is greater)

Operating Temperature

-40°F to 104°F (-40°C to 40°C)

!

Advertising