65-2451RK-05 Hydrogen Transmitter • 1

Overview

This manual describes the 65-2451RK-05 hydrogen transmitter. This manual also describes
how to install, start up, configure, maintain, and calibrate the transmitter when it is used
with a gas monitoring controller. A parts list at the end of this manual lists replacement
parts and accessories for the hydrogen transmitter.

Specifications

WARNING: Do not use this product in a manner not specified in this manual.

Table 1 lists specifications for the hydrogen transmitter.

NOTE:

The following symbol on the detector label is a caution to the user to refer to this

documentation for installation instructions:

WARNING: When using the 65-2451RK-05, you must follow the instructions and

warnings in this manual to assure proper and safe operation of the
65-2451RK-05 and to minimize the risk of personal injury. Be sure to
maintain and periodically calibrate the 65-2451RK-05 as described in this
manual.

Table 1:Specifications

Description

Specification

Target Gas

Hydrogen

Area Classification

Explosionproof for Class I, Groups B, C, and D

Sampling Method

Diffusion

Signal Output

4 to 20 mA

Detection Range

0 to 100% LEL

Response Time

90% in 45 seconds

Operating Temperature

-40°F to 167°F (-40°C to 75°C)

!