Wiring the multi-point detector to a controller – RKI Instruments 65-2485RK-02 User Manual
Page 10
Advertising

6 • 65-2485RK-02 Multi Point Detector
Figure 4: Outline & Mounting Dimensions 65-2485RK-02
2.
At the mounting site you select, use #10 screws to mount the detector to a vertical
surface.
CAUTION:
Mount the multi-point detector with the detectors facing down (see Figure 4).
NOTE:
If your application does not require a specific mounting site, mount the detector
at approximately breathing level.
Wiring the Multi-Point Detector to a Controller
WARNING: Always verify that the power source is OFF before you make wiring
connections.
1.
Turn off the controller.
2.
Turn off or unplug power to the controller.
3/4 INCH NPT HUBS (4X)
3.11
.25
Oxygen
Detector
1.10
2.40
H2S
Detector
3.00
CO
Detector
3.15
7.75
3.00
1.25
.20 DIA X .45 Slot,(2X) ,mounting
8.24 max.
Advertising