Model GD-70D4A-XX Sample Draw Transmitter • 6

Wiring the GD-70D to a Controller and AC Power

WARNING:

Always verify that power to the GD-70D4A-XX and to the controller are off and
that the controller’s and GD-70D’s power switches are in the off position before
making wiring connections or adjustments.

1.

Turn off power to the controller and the GD-70D4A-XX.

2.

Place the controller’s and GD-70D’s power switches in the OFF position.

3.

Use the conduit hubs at the bottom of the GD-70D4A-XX for routing power and signal cables
into the enclosure. Route a 3-wire power cable (18 AWG) and any relay wiring through one
conduit hub, and 2-conductor shielded cable, or two wires in conduit through the other conduit
hub to minimize crosstalk.

Figure 5: External Wiring

4.

If shielded cable is used for controller wiring, connect the signal cable shield’s drain wire to a
chassis ground at the controller, but do not connect it at the GD-70D4A-XX.

CAUTION:

Leave the cable shield’s drain wire insulated and disconnected at the
GD-70D4A-XX. You will connect the opposite end of the cable shield’s drain wire at
the controller.

CAUTION:

At the controller, do not route power and GD-70D wiring through the same conduit
hub. The power cable may disrupt the transmission of the GD-70D’s signal to the
controller.

1

2

3

4

5

6

7

+

+

-

-

ALM1

DC24V 4-20mA

ALM2

FAULT

From

Power

Supply

-

+

GD-70D Terminal Strip

8

9

10

Alarm
Device

(+) H

AC Terminal Strip

100-240 VAC

H

N

G

4 - 20 mA In (FB)

- (DC Ground)

(-) N

External Power

Source

(+) H

(-) N

External Power

Source

External Power

Source

(-) N

+ (No Connection)

Controller

Alarm
Device

Alarm
Device

(+) H