1 ABOUT THE COMMUNICATION DRIVER


•

The driver provides data exchange between SLC 5/02, 5/03 and 5/04 modular controllers, and
SATEC Powermeters via the 1746-BAS BASIC module.

•

The EPROM firmware versions can be supplied for 1 to 31 instruments. Three data sets and
three baud rates (1200, 2400 and 9600 baud) are available upon order. For available data sets,
refer to Appendix A.

•

The driver supports all models of SATEC Powermeters, although certain parameters might

not be relevant to some models, and in this case will be transmitted as zeroes.

•

The time required for polling one instrument and processing the acquired data until the data

transfer to the SLC CPU occurs is 5 to 7 seconds, depending on the model of the instrument
being polled.

•

The instruments are connected to the BASIC module's PRT2 port that is configured as ASCII

interface port. The PRT2 port can be configured for RS-422, RS-485 or RS-232
communication. When using RS-232 interface, only one Powermeter may be connected to the
BASIC module. With RS-422/RS-485 communications, up to 31 instruments can be connected to
the BASIC module in multidrop mode.