Schwank STW-JZ1 User Manual

Page 20

Advertising
background image

20

STW-JZ / IW I&O Manual

IM101229

RL: 12A- BA

RD: DEC 2010

8-A. SEISMIC RESTRAINT - LATERAL AND LONGITUDINAL

In areas prone to earthquake, or as specified on a project, install lateral and longitudinal seis-
mic restraints as indicated in Figure 11. If the heater location can be impacted by wind (aircraft
hangars, etc) refer to High Wind Restraint section 8-B.

These restraint systems indicate suspension of and attachment to the heater. The attachment
of suspension hardware to the structure will be as required by site structural conditions, instal-
lation codes, and/or local engineering design requirements. Other types or systems of restraint
may be specified by local or national codes, or by project engineering design specifications.

Schwank / InfraSave offers optional items: #2 Lion Chain 115 lb work load x 200 ft roll (PN: JL-
0800-XX); and Safety Snap Hooks (PN: JL-0800-SH = pkg 24; JL-0800-SH-B = pkg 100).
All other required seismic mounting hardware is field supplied by the installer.

8-B. HIGH WIND RESTRAINT - LATERAL, LONGITUDINAL, AND VERTICAL

In areas with wind conditions (aircraft hangers, etc) in addition to lateral and longitudinal re-
straint the heater must be restrained from vertical movement. Suspend the heater using 3/8”
threaded rod with 3” adjustment turnbuckle through a safety ring at each hanger location.

FIGURE 11

FIGURE 12

Advertising