Sensaphone fgd-0068 CARBON CO2 SENSOR User Manual

Page 3

Advertising
background image

This will enter the SETUP menu step 1, pressing the <MENU>

key a second time advances to step 2. Each press of the <MENU>

key advances the menu item. No values are saved or changed

by using the <MENU> key. The <ROLL> key is used to make

changes to program variables by scrolling through the available

options. When a value is changed, use the <SAVE> key to save it

to memory and advance to the next menu item.

<MENU> Press and release the <MENU> key to enter the SETUP

menu.

1. Out High

The default CO2 range is 0-2000 ppm. The

span can be changed from 1000 to 7500 ppm in

increments of 2000 ppm 500. Use the <ROLL>

key to change the value and <SAVE> to save.

The factory default is 2000 ppm.

<MENU>

2. Altitude

The default is 0 feet. Change by using the

<ROLL> key from 0 to 5000 feet in 500 ft

increments. Change 0 Ft for CO2 local altitude

correction and press <SAVE> to save a change.

<MENU>

3. Auto Cal

Automatic Cal Mode default is ON to correct

CO2 sensor drift to better than ± 10 ppm per

year. Change ON with the <ROLL> key and

save using <SAVE>. ON is recommended for

applications where the CO2 level will be close

to normal (400 ppm) at least once per day. If a

building is occupied 24 hours and the CO2 level

is fairly constant then this should be set to OFF.

<MENU>

4. Output

Use the <ROLL> key to toggle the output OFF

(normal operation), MIN (minimum output) or

MAX Test OFF (maximum output) for testing

purposes. Press either <SAVE> or <MENU> to

set it back to OFF and advance to the next item.

<MENU>

5. Calibrat

This item is used for 1000 ppm gas calibration

and is explained in the Calibration section.

1000 PPM
<MENU>

6. BackLite

Use the <ROLL> key to enable or disable the

LCD backlight. When enabled the backlight is

always on, Enable when disabled it never lights.

Press the <SAVE> key to save the setting. The

factory default is Enable.

<MENU>

7. Restore

Press the <SAVE> key to restore all factory

defaults and calibration to original factory

settings.

<MENU>

8. Menu

Press <SAVE> to exit the menu and return to

normal operation or <MENU> to repeat the

menu.

General Specifications
Power Supply . . . . . . . . . . . . 20 – 28 Vac/dc (non-isolated half-

wave rectified)

Consumption . . . . . . . . . . . . 100 mA max @ 24 Vdc, 185 mA max

@ 24 Vac (with all options)

Output Signals . . . . . . . . . . . 4-20 mA active (sourcing), 0-5 Vdc

or 0-10 Vdc (field selectable)

Output Drive Capability . . . 550 ohms maximum for current out-

put, 10 Kohm min for voltage output

Output Resolution . . . . . . . . 10 bit PWM
Protection Circuitry . . . . . . . Reverse voltage protected, overvolt-

age protected

Operating Conditions . . . . . 0-50 °C (32-122 °F), 0-95 %RH

non-condensing

Wiring Connections . . . . . . Screw terminal block (14 to 22 AWG)
Sensor Coverage Area . . . . . 100 m2 (1000 ft2) typical
Enclosure . . . . . . . . . . . . . . . Wall mount enclosure, 3.3”w x 4.7”h

x 1.15”d (84 x 119 x 29 mm)

CO2 Signal
Measurement Type . . . . . . . Non-Dispersive Infrared (NDIR),

diffusion sampling

Measurement Range . . . . . . 0-2000 ppm standard, programmable

up to 7500 ppm

Standard Accuracy . . . . . . . . ± 75 ppm @ 1000 ppm @ 22 °C (72

°F) compared to certified calibration

gas

Temperature Dependence . . 0.2 %FS per °C
Stability . . . . . . . . . . . . . . . . . < 2 %FS over life of sensor (15 year

typical)

Pressure Dependence . . . . . . 0.13 % of reading per mm Hg
Altitude Correction . . . . . . . Programmable from 0-5000 ft via

keypad

Response Time . . . . . . . . . . . < 2 minutes for 90 % step change

typical

Warm-up Time . . . . . . . . . . . < 2 minutes
LCD Display
Resolution . . . . . . . . . . . . . . . 1 ppm CO2
Size . . . . . . . . . . . . . . . . . . . . . 1.4” w x 0.6” h (35 x 15 mm) alpha-

numeric 2 line x 8 characters

Backlight . . . . . . . . . . . . . . . . Enable or disable via keypad