INSTALLATION
6"
[152mm]
10"
[254mm]
Max. 36"
Horizontal
Min. 36"
Vertical
Rise
WALL EXIT CLEARANCE FACTORY BUILT CHIMNEY
When a metal prefabricated chimney is used, the manufacturer's installation instructions must be followed. You must also purchase and install the ceiling 
support package or wall pass-through and "T" section package, fi restops (where needed), insulation shield, roof fl ashing, chimney cap, etc. Maintain proper 
clearance to the structure as recommended by the manufacturer. The chimney must be the required height above the roof or other obstructions for safety and 
proper draft operation.
Minimum vertical of 36" before any offset.
Horizontal Maximum of 36" with 1/4" rise per foot.
NOTE: Recommend using 2-45º instead of 90º to improve draft 
 
and
performance.
6"
[152mm]
Min. 36"
Vertical
Rise
Max. 36"
Horizontal
10"
[254mm]
MASONRY CHIMNEY
Ensure that a masonry chimney meets the minimum standards of the 
National Fire Protection Association (NFPA) by having it inspected 
by a professional. Make sure there are no cracks, loose mortar or 
other signs of deterioration and blockage. Have the chimney cleaned 
before the stove is installed and operated. When connecting the 
stove through a combustible wall to a masonry chimney, special 
methods are needed.
Minimum vertical of 36" before any offset.
Horizontal Maximum of 36" with 1/4" rise per foot.
NOTE: Recommend using 2-45º instead of 90º to improve draft 
 
and
performance.