NOTE: Built In Sensor Wiring Error Detection

• The active filter has an automatic sensor wiring

error detection algorithm built in to the
controls.

• If a sensor wiring error is detected please

reference the Sensor Error Auto Detection
section of the full user manual available at
www.transcoil.com.


3) Home screen check

• Compare “Freq” to expected line frequency
• Compare “Supply Voltage” to expected

line voltage

• “Current” expected to be zero because unit is

not running and CT inputs are shorted

• If status indicates a Fault, press “Stop” button

to reset condition


4) Status screen check

• Press “Status” to navigate to Status screen
• Compare “Volts” to expected line voltage
• Compare “Freq” to expected line frequency

• “Current” expected to be zero if unit is not

running and CT inputs are shorted


5) Phase rotation check

• Press “Phase to Neutral Voltage Plot”
• Check that the current peaks follow the

following sequence from left to right: Phase A
(green), Phase B (blue), Phase C (red)

• Equipment is phase rotation sensitive, if phase

rotation is incorrect, power down unit and
rewire to adjust phase rotation by swapping
two incoming phase connections

Warning

Improper operation will occur when
input voltage phase rotation is
incorrect.