Replacement parts, Troubleshooting, Master / drone control parts worksheet – Titus Analog T3SQ-1 IOM User Manual

Page 4

Advertising
background image

T3SQ-1-IOM-4.0

6-6-09

All rights reserved. No part of this work may be reproduced or transmitted in any form or by any means, electronic or mechanical, including photocopying and recording, or by any information storage retrieval system without permission in writing from Air Distribution Technologies.

Note: This IOM is meant to demonstrate general dimensions of this product. The drawings on this IOM are not meant to detail every aspect of the product with exactness. Drawings are not to scale.

TITUS reserves the right to make changes without written notice.

Replacement Parts

Inlet

Size

120V Inlet Heater

6

8

10

12

0.75

1.0

1.25

1.25

kW

277V Inlet Heater

0.75

1.0

1.5

2.0

kW

Part Number

31633501

31633504

31633507

31633510

Part Number

31633503

31633506

31633509

31633512

Description

Part Number

Master Controller / Thermostat

T

3

PM - 120V/24VAC Power Module

Blue RJ-45 Power and Control Cable

White RJ-12 Power Cable

Actuator / Control Disc Assembly

Supply Air Temperature Changeover Sensor

Wiring Interface Box

Venturi Tube

Venturi Tube Guide

Control Disc Sleeve

Analog Induction Channel

Plaque / Actuator / Control Disc Assembly for T3SQ-1

18200601

31673701

31623701

31623601

31623301

31625601

31623401

72540201

72540301

72540401

31623101

31625201

Master / Drone Control Parts Worksheet

# of Master units

# of Master Controller / Thermostats

= # of Master Controller / Thermostats needed

= # of White RJ-12 Power Cables needed

# of total T

3

SQ-1 diffusers

= # of Blue RJ-45 Power and Control Cables needed

# of total T

3

SQ-1 diffusers divided by 6

= # of T

3

PM Power Modules needed – FOR NON-ELECTRIC REHEAT UNITS

This worksheet is to be used to calculate the quantity of Master Controllers / Thermostats, Cables, and Power Modules needed to

make operational T

3

SQ masters and drones. See the Wiring section of this IOM for wiring information.

# of total T

3

SQ-1 diffusers divided by 5

= # of T

3

PM Power Modules needed – FOR ELECTRIC REHEAT UNITS

OR

208V Inlet Heater

0.75

1.0

1.5

2.0

kW

Part Number

31633502

31633505

31633508

31633511

Troubleshooting

Symptom

Action

No display on master

controller / thermostat

or

Dim display on master

controller / thermostat

Verify power module wiring.

Verify cables are correct.

RJ-12, 6-pin, straight through pinout from power module to first T

3

SQ diffuser or between master T

3

SQ units

and RJ-45, 8-pin, straight through pinout from T

3

SQ diffuser to master controller / thermostat.

Verify cable continuity with a cable tester.

Note: The Power Module has integral circuit protection that protects it from shorts in the RJ-12 and RJ-45 cabling by

shutting down the Power Module. During this process, the Power Module may heat up enough that the component

coatings emit a smell much like burnt electronics, but the transformer is NOT damaged. Replace the bad cable and

cycle power to the Power Module.

Control disk will not move

Verify that control disk cable has been properly inserted through conduit and plugged into wiring interface box on

backpan.

Verify that master units is properly connected with RJ-45 to master controller / thermostat or verify that drone units are

properly connected with RJ-45 to a master unit.

Occupant uncomfortable,

control disc closed

Adjust setpoints on master controller / thermostat.

Check supply air temperature by pushing and holding top arrow for 5 seconds.

If supply air is warmer than setpoint and setpoint is below zone temperature, damper will close to reduce

supply air volume into space.

If supply air is cooler than setpoint and setpoint is above zone temperature, damper will close to reduce

supply air volume into space.

Control disk will not go to

full closed

Adjust brass nuts at the top of the actuator shaft to desired minimum position.

Supply air temperature

reading is incorrect

Verify that the supply air temperature sensor is securely connected on all master units – thermostat display will show

“00” if the supply air temperature sensor is not connected.

Verify that the supply air temperature sensor has been disconnected from all drone units – thermostat display will read

incorrectly if drone units has a supply air temperature sensor.

Unit is operating in reverse

(closing when it should be

opening, etc.)

Follow steps in “Occupant uncomfortable” above to ensure proper setpoints and verify supply air temperature.

Follow steps in “Supply air temperature reading is incorrect” above to ensure supply air temperature is correct.