Problem

Possible Cause

Possible Solution

Disconnect or circuit breaker

Fuses

Manual reset cutout

Air switch

Automatic reset thermal cutout

P E switch

Electronic controller

Heater will not

operate or heat

Element wire burned out

Transformer

Heat contactor

Wiring problem

May be in off position

May be blown, wrong amp size; replace with new fuses of

correct size

If opened, manually reset it

Insufficient air flow or tube is disconnected from air

pickup probe to air switch

Opened circuit from over heating, increase airflow

Check if wired DA/NC or RA/NO terminal and common

Check to see if controller is setup for proper heat

sequence
Use ohm meter to check for resistance, no resistance,

replace with new elements
Check to see if getting 24 volts on secondary side +/-2

volts or replace new
Won't close contacts with power to holding coil terminals;

replace with new contactor

Check if correctly wired per wire diagram

Heater cycles

Not sufficient air flow at times, increase airflow

Short on volt amps for full operation of equipment; need

larger transformer
Transformer under sized or air switch not staying closed;

need larger transformer or more air for air switch
Increase air flow or look for insulation obstructing airflow

over coil

Air switch opening and closing

Transformer

Contactor chattering

Automatic reset thermal cutout

Troubleshooting - Problems and Possible Solutions

EHeat-IOM-10.0

6-1-01