3

INSTALLATION 5

Four thermal insulating blanket strips are supplied. The strips are to be

laid between adjacent tee bars and the collar as depicted. No retaining

wire is required. All fasteners must be No. 8 sheet metal steel screws,

3

/

16

” tubular steel rivets, or

1

/

4

” minimum tack welds. Use a minimum of

two connections per side for rectangular or square dampers and three

equally spaced connections for round dampers. Space fasteners a max-

imum of 6” apart. A maximum of

1

/

8

” (

1

/

4

” total) clearance must exist

between the ceiling damper and diffuser or duct drop.
In each installation, all screw or rivet attachments shall be placed a min-

imum of

3

/

16

” from the edge of the damper frame, duct drop, or diffuser

frame. All dampers must be supported by No. 16 SWG, 1

1

/

2

” cold-rolled

steel channels adjacent to both sides of the duct drop with a No. 12

SWG vertical (not splayed) hanger wire at each end.
As an alternate, two hanger straps may be used with a No. 12 SWG

hanger wire support from each strap to structural members.
Hanger straps may be factory supplied (optional) or may be field fabri-

cated from 1” wide x 3” long strips of No. 20 gauge galvanized steel.

Form as shown in Hanger Strap Detail. Fasten hanger strap to damper

frame using

3

/

16

” tubular steel rivets. Rivets must not interfere with oper-

ation of the damper blades.

7

6

2

5

3

4

1

8

5

3

4

ITEM DESCRIPTION

1. Damper
2. Diffuser (No. 24 Gauge Minimum)
3. Ceiling Grid (UL Classified)
4. No. 12 Gauge Steel Wire
5. No. 16 Gauge Steel Wire
6. Ceiling Material (UL Classified)
7. Thermal Insulating Blanket
8. Hanger Strap

ITEM DESCRIPTION

(Installations 4 and 5)

1. Damper
2. Diffuser Frame (No. 24 Gauge Minimum)
3. #8 Sheet Metal Steel Screw (see text)
4. Ceiling Grid (UL Classified)
5. No. 12 Gauge Steel Wire
6. No. 16 Gauge Steel Wire
7. Ceiling Material (UL Classified)
8. Thermal Blanket Insulation
9. Hanger Strap

10. Diffuser (Metallic or Non-Metallic)

18 x 18 Neck Size and Smaller

Installation 4

Any Size Unit with

2

10

4

7

5

8

3

6

9

6

1

6

2 3/4" MAX.

7

4

8

5

Installation 5

10

2

2" max.

1

3

CAUTION: Replace the thermal insulating blanket if it is damaged

during shipment or installation.