8.7
Electric Heater(s) (Optional)
8.7.1
The heater is fastened to the discharge collar at the blower outlet with sheet metal
screws.
8.7.2
In case of heater failure, follow the procedure described below:
8.7.3
Disconnect all power sources before attempting to open the unit. Check all electrical
wiring to ensure the unit is fully isolated.
8.7.4
Unscrew the front access panel and expose the heater(s).
8.7.5
If the thermal cut-out switch is defective, disconnect the electrical wires and unscrew
it from the heater assembly. Obtain a replacement from TITUS and
reinstall.
8.7.6
If the heating element (the spiral resistance wire) is burned out, unscrew the heater
assembly from the fan deck, disconnect the terminals and replace with a new heater
obtained from TITUS.
***When contacting TITUS for replacement parts, always
refer to the complete Model, Order and Line numbers on the Serial
Plate located on the blower housing.