Weidmuller ConnectPower 12.5A Power Supply User Manual

Page 2

Advertising
background image

300W Power Supply

Catalog Number: 991625 0024

ANALOG OUTPUTS - Monitor V, T, I

FAULT - Red LED

CURRENT LIMIT - Yellow LED

DC ON - Green LED

• Span 0-10Vdc
• Voltage output 0-30V
• Temperature output 0-100ºC
• Current output 0-15A
• Accuracy ±3% worst case over full span and temperature range
• Output impedance 2K
• Permanent short circuit protected.

This LED is not illuminated under normal operating conditions. If it turns on, one of the following faults has occurred:
• Dead short circuit.
• Output voltage has exceeded 30Vdc (overvoltage)
• Output voltage has gone below 15Vdc (undervoltage)
• The internal heatsink temperature has exceeded 100ºC.

When illuminated the output voltage drops to zero and the Fault Relay de-energizes. In order to reset the fault condition the power must
be removed from the power supply until the fault LED turns off (approx. 10 seconds).

This LED indicates that the power supply is operating within acceptable parameters.

This LED will illuminate if the output current exceeds 13.5A. The supply will deliver 18A for 300mS, with an ouput voltage of 24Vdc. Above
18A and around 300mS the output voltage will drop until the undervoltage threshold is exceeded. In this mode the supply will shut down
and auto-restart.

Weidmuller Ltd.

10 Spy Court

Markham, ON L3R 5H6

Canada

Phone: 905-475-1507

Fax: 905-475-5855

Input:

85-265Vac, 50/60Hz.

100-200Vdc, L= +, N= -
Active PFC (.99 power factor under all load conditions)

Output:

22-28Vdc, (300W max. continuous)

20mVac RMS max. ripple @ 120Hz
2mVac p-p max. ripple @ 100KHz

Advertising