Wa/l3s sound data matrix (dba @ 10 feet), Wa/l4s sound data matrix (dba @ 10 feet), Wa/l5s sound data matrix (dba @ 10 feet) – Bard Wall Mount AIr Conditioners WA5S User Manual

Page 9

Advertising
background image

Form No.

S3378-313

Supersedes S3378-1112
Page

9 of 12

Typical Sound Performance with Installation/Isolation Curbs & Acoustical Plenums

WA/L3S Sound Data Matrix (dBA @ 10 feet)

Unit Mounting

Direct

WMICF-5

Isolation

Curb

Direct

Direct

WMICF-5

Isolation

Curb

WMICF-5

Isolation

Curb

Supply Air Treatment

Grille

WAPFB51

Free Blow
Supply Air

Plenum

Standard

Supply Duct

Standard

Supply Duct

Standard

Supply Duct

WAPS51-G

Supply Air

Silencer

Return Air Treatment

Grille

WAPR11-X

Return Air

Silencer

Grille

WAPR11-X

Return Air

Silencer

Blower Only Operation

with CRV

37.8

30.7

33.6

33.6

27.4

27.6

Compressor Stage 1

Operation with CRV

51.8

40.7

49.9

41.7

39.7

38.7

Compressor

Stage 2 Operation

52.3

41.4

50.8

42.4

40.8

39.9

Compressor Stage 2 with

ERV High Speed Operation

52.7

41.7

51.7

²

²

42.9

Indoor Integrated dBA

43.8

35.0

40.7

37.2

32.8

32.6

Compressor Stage 2

Outdoor Sound Level

66.9

66.9

66.9

66.9

66.9

66.9

Note 1: dBA is sound pressure measured 10 feet in front of unit and 5 feet above floor.
Note 2: Unit or isolation curb is mounted to frame construction.
Note 3: Results may vary depending upon other factors such as room size, type of construction and acoustical variances.

WAPR11-X Return Air

Silencer

Ducted Supply Configuration

Free Blow Configuration

WA/L4S Sound Data Matrix (dBA @ 10 feet)

Unit Mounting

Direct

WMICF-5

Isolation

Curb

Direct

Direct

WMICF-5

Isolation

Curb

WMICF-5

Isolation

Curb

Supply Air Treatment

Grille

WAPFB51

Free Blow
Supply Air

Plenum

Standard

Supply Duct

Standard

Supply Duct

Standard

Supply Duct

WAPS51-G

Supply Air

Silencer

Return Air Treatment

Grille

WAPR11-X

Return Air

Silencer

Grille

WAPR11-X

Return Air

Silencer

Blower Only Operation

40.1

38.9

38.4

34.5

32.8

28.2

Compressor

Stage 1 Operation

52.0

41.4

50.9

41.2

40.5

39.0

Compressor

Stage 2 Operation

53.7

44.0

52.9

44.3

42.0

40.5

Compressor Stage 2 with

ERV High Speed Operation

55.0

46.2

54.0

²

²

44.8

Indoor Integrated dBA

45.4

40.4

44.0

37.8

35.8

33.0

Compressor Stage 2

Outdoor Sound Level

65.0

65.0

65.0

65.0

65.0

65.0

Note 1: dBA is sound pressure measured 10 feet in front of unit and 5 feet above floor.
Note 2: Unit or isolation curb is mounted to frame construction.
Note 3: Results may vary depending upon other factors such as room size, type of construction and acoustical variances.

Free Blow Configuration

Ducted Supply Configuration

WAPR11-X Return Air

Silencer

WA/L5S Sound Data Matrix (dBA @ 10 feet)

Unit Mounting

Direct

WMICF-5

Isolation

Curb

Direct

Direct

WMICF-5

Isolation

Curb

WMICF-5

Isolation

Curb

Supply Air Treatment

Grille

WAPFB51

Free Blow
Supply Air

Plenum

Standard

Supply Duct

Standard

Supply Duct

Standard

Supply Duct

WAPS51-G

Supply Air

Silencer

Return Air Treatment

Grille

WAPR11-X

Return Air

Silencer

Grille

WAPR11-X

Return Air

Silencer

Blower Only Operation

40.3

33.3

35.1

34.8

33.5

31.1

Compressor

Stage 1 Operation

52.6

40.8

50.6

43.6

40.9

39.9

Compressor

Stage 2 Operation

56.7

45.3

51.6

46.8

44.5

43.2

Compressor Stage 2 with

ERV High Speed Operation

57.8

47.1

55.0

²

²

45.4

Indoor Integrated dBA

46.2

37.2

41.8

39.0

37.2

35.4

Compressor Stage 2

Outdoor Sound Level

65.4

65.4

65.4

65.4

65.4

65.4

Note 1: dBA is sound pressure measured 10 feet in front of unit and 5 feet above floor.
Note 2: Unit or isolation curb is mounted to frame construction.
Note 3: Results may vary depending upon other factors such as room size, type of construction and acoustical variances.