2 run time fault messages – Baumfolder BAUM15: Pile Folder 1st Station (from 1999 thru 2005) User Manual

Page 24

Advertising
background image

TP10290-1

PAGE 24

6.2 Run Time Fault Messages

Run time fault messages are only displayed when the unit is in Run mode. Fault errors can still occur, but the corresponding

fault message will not be displayed until the unit is switched to Run mode. Run time fault messages are PLC System Errors

or errors in the whole Electric System. It is necessary to call a technician or service.

ENGLISH

GERMAN

CODES

TYPE

DESCRIPTION

DCT X.X.X DCT X.X.X

DCT X.X.X Information

This is the Software-Version(X.X.X)

Note: do not push any buttons until this message has been

cleared from the display

K5 Relay

K5 Relay

Error 7

PLC System

The drive stop relay, K5, is not responding to the controller.

Error

Action: Call service.

Button

Taste

Error 8

Electrical

A push button is in the wrong state during the version message

System

display. Action: Check Buttons & Cycle Power. If error

Error

persists call service.

Watchdog

Watchdog

Error 9

PLC System

The Watchdog Timer has elapsed without being serviced.

Error

Action: Cycle Power. If error persists call service.

No Tach

Impuls

Error10

Electrical

The Machine Tachometer is reading a velocity outside of the

System

range 10 – 230 meters per minute, while the main drive should

Error

be running. Action: Check the electric. If error persists call

service.

Overload

Uberlast

Error11

Electrical

A Thermal Overload has been tripped.

System

Action: Check the electric. If error persists call service.

Error

Pile Err

Spg.Uber

Error12

Electrical

The Pile Safety Relay is stuck on or there is no power supply to

System

the pile circuits. Action: Check the condition of Relay 1 (K1),

Error

Fuses F1 and F2, and X18, then cycle Power. If error persists

call service.

Overrun

Uberlauf

Error13

Electrical

The Pile Table has moved past its safety stops. Action: Check

System

the limit switches, pile table, and wiring. If error persists call

Error

service.

2

nd

Stat

2Station

Error14

Electrical

The Emergency Stop, Wrong Sheet, and Thermal Overload

System

sense circuits are all indicating failure. Likely cause is Second

Error

Station connector problems. Action: Check the Second Station

Connector, connector X22, and each individual circuit. If error

persists call service.

Suction

Saugtakt

Error15

Electrical

Short circuit on Suction controller. Action: Check the electrics.

System

If error persists call service.

Error

Table 17. Run Time Fault Messages

Advertising