Chapter 5 maintenance, Troubleshooting, Maintenance – Bird Technologies 8251 Series-Manual User Manual
Page 21: Troubleshooting maintenance
 
11
Chapter 5
Maintenance
This chapter covers cleaning, inspection, trouble-shooting, and specifications for the Bird 8251 series loads.
Troubleshooting
The table below contains troubleshooting information for problems which can occur during normal operation. This 
manual cannot list all malfunctions that may occur, or their corrective actions. If a problem is not listed or is not cor-
rected by the listed actions, notify a qualified service center.
Maintenance
Problem
Possible Cause
Correction
Leaking coolant
Loose clamping band
Tighten the clamping band
Defective or improperly installed 
front O-ring
Replace the O-ring
(See “Load Resistor” on page 15)
Defective or improperly installed 
rear O-ring
Replace the O-ring
(See “Rear Seal” on page 14)
High or low DC 
resistance
Loose RF input connector
Tighten connector
Faulty RF input connector
Models with “QC” type connectors: Replace 
connector (See “RF Connector” on page 13)
All other models: Return the unit for service
Faulty resistor
Replace the resistor
(See “Load Resistor” on page 15)
Overheating radiator
RF power too high
Lower RF power (See “Specifications” on page 17 
for maximum RF power)
Coolant level too low
Check the coolant level. Add coolant if necessary 
(See “Coolant” on page 12)
Coolant degraded
Replace the coolant
(See “Coolant” on page 12)
Faulty resistor
Replace the resistor
(See “Load Resistor” on page 15)
WARNING
Never attempt to connect or disconnect RF equipment from the transmission line while RF power is being
applied. Leaking RF energy is a potential health hazard.
WARNING
Disconnect the unit from all power sources before servicing. The unit may be energized from multiple sources.
The potential for electric shock exists.