Bryant T1--NAC User Manual

Bryant Control panel

Advertising
background image

Installation Instructions

T1--NAC

T1--NHP

LEGACY LINE--RNC

NON--PROGRAMMABLE THERMOSTAT

A07110

Legacy Line---RNC Non---Programmable Thermostat

NOTE: Read the entire instruction manual before starting the
installation.

TABLE OF CONTENTS

PAGE

SAFETY CONSIDERATIONS

1

. . . . . . . . . . . . . . . . . . . . . . . . .

INTRODUCTION

1

. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

INSTALLATION CONSIDERATIONS

1

. . . . . . . . . . . . . . . . . . .

INSTALLATION

1

. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

Step 1 — Thermostat Location

1

. . . . . . . . . . . . . . . . . . . . . . . .

Step 2— Install Thermostat

2

. . . . . . . . . . . . . . . . . . . . . . . . . . .

Step 3 — Set Thermostat Configuration

2

. . . . . . . . . . . . . . . . .

Step 4 — Thermostat Operation

3

. . . . . . . . . . . . . . . . . . . . . . . .

Step 5 — Check Thermostat Operation

3

. . . . . . . . . . . . . . . . . .

WIRING DIAGRAMS

4

. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

SAFETY CONSIDERATIONS

Read and follow manufacturer instructions carefully. Follow all

local electrical codes during installation. All wiring must conform

to local and national electrical codes. Improper wiring or
installation may damage thermostat.

Recognize safety information. This is the safety--alert symbol

.

When you see this symbol on the equipment and in the instruction
manual, be alert to the potential for personal injury. Understand the

signal words DANGER, WARNING, and CAUTION.
These words are used with the safety--alert symbol. DANGER

identifies the most serious hazards which will result in severe

personal injury or death. WARNING signifies a hazard which
could result in personal injury or death. CAUTION is used to

identify unsafe practices which may result in minor personal injury

or product and property damage. NOTE is used to highlight
suggestions which will result in enhanced installation, reliability, or

operation.

INTRODUCTION

The Legacy Line--RNC Series thermostat is an electronic 24VAC,

non--programmable, manual changeover wall mount thermostat.

This thermostat uses a single setpoint to maintain and control room
temperature in both the heating and air conditioning modes. The

thermostat is designed to maintain +/-- 2_F accuracy. No batteries
are required; temperature, fan, mode, and installer configuration

settings are preserved with power off.

INSTALLATION CONSIDERATIONS

Air Conditioner Model

T1--NAC, Legacy Line--RNC Series Model air conditioner
thermostat, may be wired with or without connecting a common

wire between the indoor equipment and the thermostat. However, it
is recommended to use a common wire whenever possible.

Without a common wire this thermostat becomes “power stealing.”

This means it will need to steal a small amount of power from the
equipment to which it is connected.
NOTE: Not all HVAC equipment is compatible with power
stealing type thermostats. All Bryant equipment is directly
compatible with this thermostat except the Thermostat Conversion
Kit, Part #TSTATXXCNV10. For all non--Bryant equipment,
consult the system equipment Installation Instructions before
applying this thermostat in a power stealing manner.

Heat Pump Model

T1--NHP, Legacy Line--RNC Series Model heat pump thermostat,
is compatible with all Bryant heat pump systems. It is NOT power

stealing and MUST have both the R and C terminals connected to

operate properly. This thermostat uses a green LED to indicate
auxiliary heat and emergency heat operation.

INSTALLATION

Step 1 — Thermostat Location

Thermostat should be mounted:

S

Approximately 5 ft (1.5m) from floor.

S

Close to or in a frequently used room, preferably on an
inside partitioning wall.

S

On a section of wall without pipes or duct work.

Thermostat should NOT be mounted:

S

Close to a window, on an outside wall, or next to a door
leading to the outside.

S

Exposed to direct light and heat from the sun, a lamp,
fireplace, or other heat--radiating object which may cause
a false reading.

S

Close to or in direct airflow from supply registers and
return--air grilles.

S

In areas with poor air circulation, such as behind a door
or in an alcove.

Advertising
This manual is related to the following products: