5— gross cooling capacities (mbh) continued – Bryant CK5A User Manual

Page 5

Advertising
background image

—5—

GROSS COOLING CAPACITIES (MBH) Continued

CFM

— Cubic Ft per Minute

EWB

— Entering Wet Bulb (°F)

LWB

— Leaving Wet Bulb (°F)

TC

— Total Cooling Capacity 1000 Btuh

SHC

— Total Sensible Capacity 1000 Btuh

BF

— Bypass Factor

MBH

—1000 Btuh

NOTES:

1. Contact manufacturer for cooling capacities at conditions other than

shown in table.

2. Formulas:

Leaving db = entering db —

Leaving wb = wb corresponding to enthalpy of air leaving coil (h

LWB

)

h

LWB

= h

EWB

where h

EWB

= enthalpy of air entering coil.

UNIT

SIZE

INDOOR COIL

AIR

SATURATED TEMPERATURE LEAVING EVAPORATOR (°F)

30

35

40

45

50

CFM

EWB

TC

SHC

BF

TC

SHC

BF

TC

SHC

BF

TC

SHC

BF

TC

SHC

BF

A060
N060
T060

1600

72

101.0

46.7

0.00

90.8

42.2

0.00

80.4

37.6

0.12

69.1

33.0

0.08

56.0

28.0

0.07

67

83.8

49.9

0.07

73.5

45.2

0.07

63.1

40.5

0.06

51.1

35.3

0.06

38.0

29.8

0.08

62

68.7

53.0

0.07

58.2

48.0

0.07

47.7

43.0

0.07

38.2

37.6

0.11

31.6

31.6

0.24

2000

72

113.0

52.2

0.00

102.0

47.4

0.00

90.4

42.6

0.14

77.5

37.5

0.11

63.5

32.3

0.10

67

94.0

56.8

0.10

82.6

51.8

0.10

71.2

46.8

0.09

58.5

41.3

0.10

43.7

35.2

0.11

62

77.0

61.2

0.09

66.0

56.0

0.10

55.1

50.7

0.10

45.0

44.7

0.15

37.3

37.3

0.28

2400

72

123.0

56.6

0.26

111.0

51.6

0.21

98.4

46.7

0.16

84.2

41.2

0.13

69.4

35.8

0.13

67

103.0

62.8

0.13

89.9

57.4

0.13

77.3

52.0

0.12

64.3

46.5

0.12

48.3

40.0

0.14

62

83.0

68.4

0.11

72.2

63.0

0.12

61.4

57.5

0.13

51.1

51.1

0.18

42.5

42.5

0.32

X060

1600

72

106.0

49.0

0.00

94.4

44.0

0.00

83.1

39.0

0.07

71.6

34.3

0.05

58.4

29.1

0.06

67

85.7

51.3

0.05

75.4

46.5

0.05

65.1

41.7

0.05

52.9

36.4

0.05

39.8

30.9

0.07

62

70.8

54.8

0.04

59.6

49.2

0.05

48.4

43.7

0.06

38.0

37.2

0.13

31.1

31.1

0.26

2000

72

116.0

53.7

0.18

105.0

49.2

0.14

94.7

44.7

0.10

81.6

39.5

0.08

67.3

34.0

0.08

67

97.6

59.1

0.07

86.1

54.0

0.07

74.5

48.8

0.07

61.4

43.1

0.07

46.4

36.9

0.09

62

80.0

64.0

0.05

68.4

58.1

0.07

56.8

52.1

0.09

45.0

44.7

0.16

37.4

37.4

0.29

2400

72

128.0

59.4

0.17

116.0

54.4

0.15

104.0

49.4

0.12

89.9

43.9

0.10

74.1

38.0

0.10

67

108.0

66.0

0.09

94.7

60.4

0.09

81.8

54.7

0.10

67.9

48.8

0.10

51.9

42.3

0.11

62

86.4

71.3

0.08

75.0

65.4

0.10

63.6

59.5

0.12

52.1

52.1

0.17

43.3

43.3

0.31

sensible heat cap.

1.09 x CFM

total capacity (Btuh)

4.5 x CFM

3. Direct interpolation is permissible. Do not extrapolate.
4. SHC is based on 80°F db temperature of air entering coil.

Below 80°F db, subtract (Correction Factor x CFM) from SHC.
Above 80°F db, add (Correction Factor x CFM) to SHC.

5. All data points are based on 10°F superheat leaving coil.
6. Bypass Factor = 0 indicates no psychometric solution. Use bypass

factor of next lower EWB for approximation.

Interpolation is permissible.
Correction Factor = 1.09 x (1 – BF) x (db – 80)

BYPASS
FACTOR

ENTERING AIR DRY BULB TEMPERATURE (°F)

79

78

77

76

75

Under 75

81

82

83

84

84

Over 85

Correction Factor

0.10

0.98

1.96

2.94

3.92

4.91

Use formula

shown below

0.20

0.87

1.74

2.62

3.49

4.36

0.30

0.76

1.53

2.29

3.05

3.82