6. Find Wire Size for two conductors:

 

PAR 000 Cu

WIRE SIZE

7. Exit Free Air Mode and Clear:

  

60 Cu

0.

Finding Derated Wire Size

A circuit was built with 60°C Copper

wire connecting a 47,650 VA load

to a 240 Volt, 3Ø source. Ambient

Temperature is 50°C. What is the

Derated Wire Size required if eight

current-carrying THHN wires are

installed in the raceway?

KEYSTROKE

DISPLAY

 

0.

1. Set to 3-Phase:

 

(3Ш)

3 Ph

2. Set to 60º C:

 

(60º)

60

3 Ph

3. Set to Copper (if necessary):

 

(

Cu/Al

)

60 Cu

3 Ph

4. Enter Volt-Amps:

     

VA 47,650.

5. Enter Volts:

   

VOLT 240.

6. Find Amps:

AMPS 114.62808.