DRY COIL AIR DELIVERY* — VERTICAL DISCHARGE

(Deduct 10% for 208 v)

UNIT

SIZE

588A

MOTOR

SPEED

230 AND 460 VOLT VERTICAL DISCHARGE

External Static Pressure (in. wg)

0.0

0.1

0.2

0.3

0.4

0.5

0.6

0.7

0.8

0.9

1.0

018

Low

Watts

—

295

251

223

201

176

149

124

—

—

—

Cfm

—

821

817

753

665

536

343

164

—

—

—

High

Watts

401

376

346

322

294

272

250

229

219

—

—

Cfm

1334

1253

1128

996

816

658

461

246

167

—

—

024,

030

Low

Watts

—

285

284

282

278

274

270

261

251

244

230

Cfm

—

798

761

727

682

634

581

525

450

371

304

Med

Watts

—

378

371

368

362

357

343

332

315

301

283

Cfm

—

1011

982

948

906

858

771

703

597

492

387

High

Watts

—

520

511

487

472

451

431

411

385

362

341

Cfm

—

1342

1289

1237

1181

1106

1007

892

745

610

471

036

Low

Watts

—

460

439

423

898

379

349

322

297

270

246

Cfm

—

1191

1136

1081

1005

907

795

687

579

471

349

Med

Watts

—

511

492

470

450

420

392

364

332

308

275

Cfm

—

1316

1244

1178

1104

1005

891

784

657

535

389

High

Watts

—

655

631

603

584

552

522

492

459

433

398

Cfm

—

1541

1458

1367

1292

1178

1053

920

806

662

509

042

Low

Watts

—

637

612

587

560

536

493

455

—

—

—

Cfm

—

1500

1450

1405

1350

1290

1200

1105

—

—

—

High

Watts

—

790

750

700

699

639

608

574

547

—

—

Cfm

—

1750

1625

1604

1509

1421

1323

1221

1094

—

—

048

Low

Watts

—

847

784

746

708

646

609

563

516

—

—

Cfm

—

1995

1901

1822

1730

1580

1477

1319

1178

—

—

High

Watts

—

—

909

852

820

801

751

687

639

—

—

Cfm

—

—

2018

1896

1814

1729

1582

1380

1220

—

—

060

Low

Watts

—

983

960

923

885

845

804

751

697

665

633

Cfm

—

1838

1808

1755

1702

1628

1553

1446

1339

1257

1175

Med

Watts

—

1115

1083

1045

1006

964

921

872

823

783

742

Cfm

—

2067

2023

1957

1891

1807

1723

1612

1501

1392

1282

High

Watts

—

1284

1201

1166

1131

1092

1053

1001

980

907

864

Cfm

—

2187

2108

2038

1968

1882

1796

1676

1555

1437

1318

*Air delivery values are based on operating voltage of 230 v or 460 v, dry coil, without filter. De-

duct wet coil and filter pressure drops to obtain external static pressure available for ducting.

NOTES:
1. Do not operate the unit at a cooling airflow that is less than 350 cfm for each 12,000 Btuh of

rated cooling capacity. Evaporator coil frosting may occur at airflows below this point.

2. Dashes indicate portions of table that are beyond the blower motor capacity or are not

recommended.

18