ALTERNATIVES FOR WALL PROTECTION


Example: The rear clearance for the Model 80 from page 12 is 26". (Measurement A.) This clearance may be
reduced by 66% by using either of the wall protection devices mentioned below.

Tested and Listed Wall Protector


Clearances to combustibles may be reduced if a tested and listed wall protector is installed over a combustible
surface when the following condition exist:
1. A dead air space or 1" separates the listed and tested wall protector from the combustible surface.
2. The tested and listed wall protector extends from floor to ceiling with a 1" clearance for air circulation at both

the floor and ceiling.

3. The 1" spacers (preferable ceramic rather than metal) must be located at the corners rather than behind the

heater or the chimney connector.

Unlisted and Untested Wall Protector


Wall protectors may be constructed of masonry, 24 gauge or thicker sheet metal, or non-combustible 1/2" thick
insulation board. Conditions 2 and 3 above must be observed but the air space in condition 1 must be increased to 1
1/2".

FINAL CHECK

1. Recheck the specified clearances.
2. Remove all foreign material from the firebox area.

BRICK
CLEARANCE
REDUCTION
SYSTEM

BRICK WALL SPACED
OUT 1 INCH FROM
PROTECTED SURFACE

AIR CIRCULATION

LEAVE 1 INCH
CLEARANCE FOR AIR
CIRCULATION

FLOOR

AIRSPACE

COMBUSTIBLE
WALL

1”

NAIL OR
SCREW
ANCHOR

MINIMUM
24 GAUGE
SHEET
METAL

1 INCH NON-COMBUSTIBLE SPACER SUCH AS STACKED WASH-
ERS, SMALL DIAMETER PIPE, TUBING, OR ELECTRICAL CON-
DUIT.

DO NOT USE FASTENERS DIRECTLY BEHIND CHIM-
NEY CONNECTOR OR STOVE

COMBUSTIBLE
WALL

TOP VIEW

NON-COMBUSTIBLE
SPACERS

MINIMUM
24 GAUGE
SHEET METAL

FLOOR PROTECTOR

SHEET METAL CLEARANCE REDUCTION SYSTEM

FIGURE 12

BRICK WALLS MAY BE ATTACHED TO COMBUSTIBLE WALLS
USING WALL TIES. IF BRICK IS USED, BE SURE FLOOR CAN
WITHSTAND THE WEIGHT OF THE BRICK.

COMBUSTIBLE WALL

WOOD STOVE

CLEARANCE RE-
DUCTION SYSTEM
SPACED OUT 1
INCH.