Air delivery — horizontal discharge units (cont) – Bryant 579F User Manual

Page 45

Advertising
background image

AIR DELIVERY — HORIZONTAL DISCHARGE UNITS (cont)

580D150 (12

1

2

TON)

Airflow

(Cfm)

Standard and Alternate Belt Drive Motors

External Static Pressure (in. wg)

0.2

0.4

0.6

0.8

1.0

1.2

Rpm

Bhp

Watts

Rpm

Bhp

Watts

Rpm

Bhp

Watts

Rpm

Bhp

Watts

Rpm

Bhp

Watts

Rpm

Bhp

Watts

3700

677

1.20

1129

748

1.43

1316

810

1.65

1498

869

1.89

1700

928

2.17

1940

984

2.43

2166

3800

691

1.28

1194

761

1.52

1390

822

1.75

1582

880

1.98

1776

937

2.28

2035

993

2.55

2272

3900

705

1.37

1267

773

1.62

1473

834

1.86

1674

891

2.08

1862

947

2.39

2131

1002

2.66

2370

4000

720

1.47

1349

786

1.71

1548

847

1.97

1768

902

2.19

1957

957

2.50

2228

1011

2.79

2485

4100

734

1.56

1423

800

1.82

1641

860

2.09

1871

914

2.31

2061

967

2.60

2316

1021

2.91

2593

4200

749

1.66

1506

813

1.92

1725

873

2.21

1974

926

2.44

2175

978

2.71

2414

1030

3.04

2710

4300

764

1.77

1598

826

2.04

1828

886

2.33

2079

938

2.57

2290

989

2.83

2521

1040

3.18

2837

4400

779

1.88

1691

840

2.16

1931

899

2.46

2193

951

2.71

2414

1000

2.96

2638

1050

3.31

2955

4500

793

1.99

1785

854

2.28

2035

912

2.59

2307

963

2.86

2548

1012

3.09

2755

1061

3.43

3065

4600

808

2.11

1888

868

2.42

2158

925

2.73

2459

975

3.00

2674

1024

3.25

2901

1071

3.56

3184

4700

822

2.24

2000

882

2.56

2281

937

2.86

2548

988

3.16

2819

1036

3.42

3056

1082

3.70

3313

4800

837

2.37

2114

896

2.71

2414

950

3.00

2674

1001

3.32

2964

1048

3.59

3212

1093

3.86

3461

4900

852

2.51

2237

910

2.86

2548

963

3.15

2810

1014

3.48

3111

1060

3.76

3368

1105

4.02

3609

5000

867

2.65

2361

924

3.01

2683

977

3.30

2946

1027

3.65

3267

1073

3.94

3535

1117

4.20

3776

5100

882

2.79

2485

938

3.17

2828

990

3.46

3092

1040

3.82

3424

1085

4.12

3702

1129

4.40

3962

5200

896

2.95

2629

952

3.33

2973

1003

3.63

3248

1053

4.00

3590

1098

4.30

3869

1141

4.60

4148

5300

911

3.11

2773

967

3.50

3129

1017

3.80

3405

1066

4.18

3757

1111

4.50

4055

1153

4.80

4335

5400

926

3.27

2919

981

3.68

3294

1030

3.98

3572

1079

4.35

3916

1124

4.70

4270

1166

5.01

4531

5500

940

3.44

3074

995

3.86

3461

1044

4.17

3748

1092

4.54

4093

1137

4.91

4437

1178

5.22

4726

5600

955

3.62

3239

1010

4.04

3627

1058

4.38

3943

1105

4.73

4270

1150

5.12

4633

1190

5.44

4930

5700

970

3.80

3405

1024

4.23

3804

1072

4.59

4139

1118

4.93

4456

1163

5.34

4837

1203

5.67

5143

5800

985

3.99

3581

1039

4.42

3981

1086

4.80

4335

1131

5.14

4652

1176

5.56

5041

5900

1000

4.18

3757

1053

4.62

4167

1100

5.02

4540

1144

5.36

4856

6000

1015

4.39

3953

1068

4.83

4363

1114

5.25

4754

1158

5.58

5060

6100

1030

4.59

4139

1083

5.04

4558

1128

5.48

4967

6200

1046

4.81

4344

1097

5.26

4763

1142

5.71

5180

580D150 (12

1

2

TON) (cont)

Airflow

(Cfm)

Standard and Alternate Belt Drive Motors

External Static Pressure (in. wg)

1.4

1.6

1.8

2.0

Rpm

Bhp

Watts

Rpm

Bhp

Watts

Rpm

Bhp

Watts

Rpm

Bhp

Watts

3700

1036

2.68

2387

1080

2.90

2548

1114

3.07

2737

1135

3.17

2828

3800

1046

2.81

2503

1092

3.05

2719

1129

3.25

2901

1156

3.39

3028

3900

1055

2.94

2620

1102

3.20

2855

1143

3.42

3056

1174

3.59

3212

4000

1064

3.07

2737

1112

3.34

2983

1155

3.59

3212

1190

3.80

3405

4100

1072

3.20

2855

1121

3.49

3120

1165

3.76

3368

1203

3.99

3581

4200

1081

3.34

2983

1130

3.64

3258

1175

3.92

3516

1215

4.18

3757

4300

1090

3.48

3111

1139

3.79

3396

1185

4.08

3664

1226

4.36

3925

4400

1100

3.63

3248

1148

3.94

3535

1194

4.25

3822

1236

4.54

4093

4500

1109

3.78

3387

1157

4.09

3674

1203

4.42

3981

1246

4.72

4260

4600

1119

3.93

3525

1166

4.26

3832

1212

4.58

4130

1255

4.91

4437

4700

1129

4.09

3674

1175

4.43

3990

1221

4.76

4298

1264

5.09

4605

4800

1139

4.24

3813

1185

4.60

4148

1230

4.93

4456

1273

5.28

4782

4900

1150

4.38

3943

1194

4.77

4307

1239

5.12

4633

1282

5.47

4958

5000

1161

4.54

4093

1204

4.95

4475

1248

5.31

4810

1291

5.66

5133

5100

1172

4.71

4251

1214

5.13

4642

1257

5.51

4995

5200

1183

4.91

4419

1225

5.29

4791

1267

5.70

5170

5300

1194

5.08

4596

1236

5.47

4958

5400

1206

5.29

4791

1247

5.65

5124

5500

1218

5.52

4958

5600

1230

5.75

5124

5700

5800

5900

6000

6100

6200

LEGEND

Bhp

Brake Horsepower Input to Fan

Watts — Input Watts to Motor

NOTES:

1. Boldface indicates field-supplied drive required. (See Note 6.)

2.

indicates alternate motor and/or drive required.

3.

indicates field-supplied motor and drive required.

4.

indicates maximum usable bhp/watts of standard motor and drive.

5.

indicates maximum usable bhp/watts of alternate motor and/or drive.

6. Standard drive range is 860 to 1080 rpm. Alternate drive range is 900 to

1260 rpm. All other rpms require a field-supplied drive.

7. Values include losses for filters, unit casing, and wet coils.

8. Maximum continuous bhp is 4.2 for the standard motor and 5.25 for the al-

ternate motor. The maximum continuous watts are 3775 for the standard mo-
tor and 4400 for the alternate motor. Extensive motor and electrical testing on
these units ensures that the full range of the motor can be utilized with con-
fidence. Using your fan motors up to the wattage ratings shown will not result
in nuisance tripping or premature motor failure. Unit warranty will not be af-
fected. See Evaporator-Fan Motor Performance table on page 60 for addi-
tional information.

9. Use of a field-supplied motor may affect wire sizing. Contact your local rep-

resentative to verify.

10. Interpolation is permissible. Do not extrapolate.
11. Minimum allowable cfm is 300 cfm/ton.

45

Advertising