Bryant 580F User Manual

Page 28

Advertising
background image

—

28

—

Table 8 — Fan Rpm at Motor Pulley Settings*

*Approximate fan rpm shown.

†Indicates standard motor and drive package.

**Indicates alternate motor and drive package.

††Indicates high-static motor and drive package.

Table 9 — Evaporator-Fan Motor Efficiency

NOTE: All indoor-fan motors 5 hp and larger meet the minimum effi-
ciency requirements as established by the Energy Policy Act of 1992
(EPACT) effective October 24, 1997.

UNIT 580F

MOTOR PULLEY TURNS OPEN

0

1

/

2

1

1

1

/

2

2

2

1

/

2

3

3

1

/

2

4

4

1

/

2

5

5

1

/

2

6

090,091†

840

815

790

765

740

715

690

665

635

615

590

—

—

090,091**

935

910

885

860

835

810

785

760

735

710

685

—

—

090,091††

1080

1025

1007

988

970

952

933

915

897

878

860

—

—

102,103†

935

910

885

860

835

810

785

760

735

710

685

—

—

102,103††

1080

1025

1007

988

970

952

933

915

897

878

860

—

—

120,121†

935

910

885

860

835

810

785

760

735

710

685

—

—

120,121**

1085

1060

1035

1010

985

960

935

910

885

860

835

—

—

120,121††

1130

1112

1087

1062

1037

1012

987

962

937

912

887

862

830

150,151†

1080

1060

1035

1015

990

970

950

925

905

880

860

—

—

150,151**

1130

1112

1087

1062

1037

1012

987

962

937

912

887

862

830

UNIT
580F

MOTOR EFFICIENCY

(%)

090-121

80

150,151

87

Fig. 34 — Typical Belt-Drive Motor Mounting

for Sizes 120-151

Fig. 35 — Evaporator-Fan Pulley Adjustment

Advertising