5 conversion from lever to actuator, 10 drawings, 1 legend – Richter BVIP/F Series Ball Valves (ISO/DIN) User Manual

Page 13: Conversion from lever to actuator, Legend, Series bvi/f, bvip/f

Advertising
background image

Series BVI/F, BVIP/F

Page 13

9520-090-en

Revision 10

TM 8361

Edition 10/2011

9.5 Conversion from lever to

actuator

Select the actuator in accordance with the
instructions of the actuator manufacturer.

Remove lever 203.

Remove lever stop 577 and plug.

Check the fits of the coupling 804, bracket 510
and actuator 850.

Mount bracket 510 with the opening at right angles
to the direction of flow.

Mount coupling 804 and actuator 850. Observe
the actuator position in accordance with the actua-
tor operating manual.

10 Drawings

10.1 Legend

101

main body

102

body end piece

200

ball

201

ball/stem unit

202

stem

203

lever

401

seat ring

Cone shape stem sealing
Includes:

405/1

thrust ring

422

base ring

423

packing insert

502

spring gland follower

503

packing gland follower

510

bracket

554/1

washer

557

grounding spring washer

577

lever stop

804

coupling

includes:

500

ring (option)

952

pressure spring

980/1

round head grooved pin

850

actuator

901/x

hex. screw

904/1

set screw

918/1

threaded rod

(DN 150)

920/x

hex. nut

936/x

toothed lock washer

Advertising
This manual is related to the following products: