Adjus t menu – tekmar 162 Setpoint Control Installation User Manual

Page 9

Advertising
background image

9 of 32

© 2007

D 162 - 08/07

ADJUS

T MENU

ADJUST Menu (1 of 6)

Mode

Item Field

Range

Access

Description

1
2
3
4
5
6

1, 2, 3, 4, 5, 6

Default = 1

InST

ADV

APPLICATION MODE

SECTION A - F

Select the application for the setpoint control.
1 = On / OFF Setpoint (Heat and Cool)
2 = Hot Tub (Heat only)
3 = DHW Tank (Heat only)
4 = PWM Setpoint (Heat and Cool)
5 = Floor (Heat only)
6 = Pool (Heat only)

1
4

COOL, HEAT

Default = HEAT

InST

ADV

MODE OF OPERATION

SECTION A, D

Select the mode of operation of the setpoint
control. Choose between Heat or Cool.

2
6

HEAT, OFF

Default = HEAT

USEr

InST

ADV

MODE OF OPERATION

SECTION B, F

Select to either heat or turn off the hot tub or
pool.

1
4

OFF, -4°F (-20°C)

to Setpoint

Maximum

Default = 160°F

(71.0°C)

LTD

USEr

InST

ADV

SET SETPOINT OCCUPIED

SECTION A, D

Select the setpoint temperature for the occupied
period.

Note:

In the Limited Access Level, the temperature

can only be adjusted by +/-3°F (1.5°C) from the
temperature setting entered prior to entering the
Limited access level.

1
4

OFF, -4°F (-20°C)

to Setpoint

Maximum

Default = OFF

USEr

InST

ADV

SET SETPOINT UNOCCUPIED

SECTION A, D

Select the setpoint temperature for the unoccupied
period.
Note:

This item is only available when a

programmable setback schedule has been
selected.

1
4

OFF, -4°F (-20°C)

to Setpoint

Maximum

Default = OFF

USEr

InST

ADV

SET SETPOINT AWAY

SECTION A, D

Select the setpoint temperature for the away
period.

Note:

This item is only available when scenes

are set to On.

2

OFF, 40°F

(4.5°C) to Hot Tub

Maximum

Default = 102°F

(39.0°C)

LTD

USEr

InST

ADV

SET HOT TUB OCCUPIED

SECTION

B

Select the hot tub temperature for the occupied
period.

Note:

In the Limited Access Level, the temperature

can only be adjusted by +/-3°F (1.5°C) from the
temperature setting entered prior to entering the
Limited access level.

The ADJUST Menu items are the programmable
settings used to operate the mechanical equipment.

Continued on next page.

Advertising