Outdoor reset strategy, 60 minute cycle, 45 minutes off time – tekmar 269 One Stage Steam Control User Manual

Page 2

Advertising
background image

Copyright © D 269 - 06/00

2 of 12

Most residential and small commercial steam systems can only produce

heat at a fixed rate and are either on (100% output), or off (0% output). When
100% output is not required (warmer weather), the boiler must be cycled on
and off in order to prevent overheating. Figures 1 and 2 illustrate the
operation of two heating systems with different heating cycle times.

Cycle times are selected based on the operating characteristics of each

individual heating system. Figure 1 shows a system where a 30 minute cycle
is required, and Figure 2 shows a system where a 60 minute cycle is required.
In both examples the heating plant output is exactly the same at 50%.

As the outdoor temperature changes, the % on time of the boiler should

be changed to match the changing heat losses of the building. Figure 3
illustrates how Outdoor Reset of a steam boiler changes the % on time from
0% at the Warm Weather Shut Down point, to 100% at design outdoor
conditions (coldest day of the year). Applying this chart to the system
represented in Figure 1, we see that the outdoor temperature would be at
30

°F with the 50% on time that is illustrated, and if the outdoor temperature

warmed up to 50

°F, the system would operate with a 25% on time as

illustrated in Figure 4. Using outdoor temperature to reset the % on time in
this manner can help minimize the overheating and wide temperature swings
found in many systems that use only room temperature control.

Before adding this control to a steam system, it is very important that the installer examine the

complete system and how

it works. In order to properly install and setup this control, the installer must know: the optimum cycle length and minimum on
time of the system, the outdoor temperature at which 100% boiler on time will be required, and the best locations to install
sensors. In addition to examining the boiler operation,

all other system components such as steam traps, air vents, radiators,

piping, etc. should be examined for correct operation to ensure that the system is working at its peak efficiency. If there are
existing faults that degrade the operation of the system, it is quite likely that the addition of this control could allow those faults
to have an even greater effect, making it important to correct such faults or at least point them out to the end user.

Outdoor Reset Strategy

30 minute cycle

15 minutes

on time

15 minutes

off time

15 minutes

on time

15 minutes

off time

15 minutes

on time

15 minutes

off time

15 minutes

on time

15 minutes

off time

Boiler
on

on

Boiler
off

off

off

Boiler Operation

30 minute cycle

30 minute cycle

30 minute cycle

on

off

on

off

on

Figure 1. 50% on time with a 30 minute heating cycle

60 minute cycle

60 minute cycle

Boiler on

on

Boiler off

off

30 minutes

on time

30 minutes

on time

30 minutes

off time

30 minutes

off time

off

Boiler Operation

on

Figure 2. 50% on time with a 60 minute heating cycle

Outdoor air temperature

Percentage of boiler on time per cycle

50

(10)

30

(-1)

10

(-12)

-10

°F

(-23)

°C

20%

70

(21)

0%
on time

10%

90

(32)

30%

40%

50%

60%

70%

80%

90%

100%

-30

°F

(-34)

°C

Boiler is turned on 100%

Boiler is cycled on/off

WWSD

Point

Boiler is turned off

Design

Outdoor

Temperature

Figure 3. Outdoor Reset of boiler % on time

60 minute cycle

60 minute cycle

45 minutes off time

45 minutes off time

15 minutes

on time

15 minutes

on time

Boiler
on

Boiler
off

off

Boiler Operation

on

off

on

Figure 4. 25% on time with a 60 minute cycle time

Advertising