Zone

1

2

3

4

Thermostat Load

Zone Valve Load

Floating

Action (VA)

Control

Load (VA)

Total Zone Load

+

+

+

+

+

2

Transformer

must exceed:

VA

Control Wiring

Line Voltage Wiring-----------------------------------------------------------------------------------

-----------------------------------------------------------------------------------

Ground the Pumps

Connect the pump grounds to the power supply
ground as shown in Figure 1. The ground wire must
also be grounded to the electrical box.

•

CAUTION: TURN ALL POWER OFF BEFORE PERFORMING ANY WIRING.

Pump

Leads

DHW Pump

Boil System Pump

Power Source

(L,N)

Pump

Pump

Figure 1 - Connect
Ground Wires

DHW Pump

Boil System Pump

Power Source

(L,N)

Pump

Pump

Figure 2 - Connect
Neutral Wires

Strip wires 1/2 inch
(13 mm). Installed
wires are not removable.

12-18 AWG

DHW Pump

Pump Power L

400

Boil System Pump

DHW Pump

Boil System Pump

Power

Source

(L,N)

Figure 3 - Connect
Line Voltage (Hot)

Strip wires 1/2 inch
(13 mm). Installed
wires are not removable.

12-18 AWG

DHW Pump

Pump Power L

400

Boil System Pump

DHW Pump

Power

Source

(L,N)

Boil System Pump

Figure 4 - Connect
Pump Line (Hot)

Wire the Pump Neutrals

Connect the Neutral (N) wires from each pump and wire
to the 115 V (ac) Neutral (N) wire. If the transformer has
been mounted to this electrical box, connect its neutral
wire with this group. This is shown in Figure 2.

•

Wire the Pump Power (L)

Connect the 115 V (ac) line voltage (L) wire to the red
Pump Power (L) wire on the back of the House Control
and to the 115 V (ac) side of the transformer. Use a
wire nut or approved connector. See Figure 3.

•

Wire the Pumps

Wire each remaining line voltage pump wire into the
push-in wire connector of the corresponding pump
lead on the back of the House Control. This is shown
in Figure 4.

•

The following chart is provided to simplify transformer sizing: