8.

Critical Settings

Item Field

Description

APPLICATION MODE

Select the control application mode.
PWM = Hydronic Pulse Width Modulation.
BOIL = Hydronic boiler heats snow melting
system.
MIX = Hydronic mixing valve or injection
pump heats snow melting system.
ELEC = Electric snow melt.
090 = Tandem Snow/ Ice Detection
Default = PWM

SNOW / ICE SENSOR

Select if a Snow / Ice Sensor 090 or 094, or
Snow Sensor 095 is installed.
Default = 090

SLAB SENSOR
Select if a Slab Sensor 072 or 073 is installed

to measure the slab temperature.
Default = ON

SLAB PROTECTION

Select if the slab should be protected from
large temperature differentials to avoid
cracking the concrete due to high tensile
stress.

Default = ON

OUTDOOR/BOILER RETURN SENSOR

Select if the Out/Bret wiring terminal is
connected to an outdoor sensor or a boiler
return sensor.

Default = OUT

The System Menu provides settings on how to configure and operate the mechanical equipment.

Item Field

Description

ECONOMELT

EconoMelt allows the user to mechancially
remove snow then manually start the system
to melt the thin snow layer or ice.

Default = OFF

tekmarNet

®

SYSTEM PUMP

Select if the system pump located on the
tekmarNet

®

System Control should operate

when the snow melt zone is heating.

Conditions: Application Mode is set to

PWM, Boil or Mix and Boiler Type is set

to CTRL (tN4 control).
Default = ON

AUXILIARY RELAY

Select if the auxiliary relay should function
as system pump or as an alert.

Default = SYS

MAXIMUM MELT TIME

Select to limit the amount of melting run
time.

Default = 3.0 days