Display and indicator lights operation, Testing the control functions, Testing the control functions step seven – tekmar 661 Snow Detector & Melting Control User Manual

Page 6: Operational test of control functions

Advertising
background image

6

Display and Indicator Lights Operation

Testing the Control Functions

Step Seven

Operational test of control functions

Slab
Target Slab

% Output

Usage (hours)

Time Remaining

Slab
Target Slab

% Output

Usage (hours)

Time Remaining

Slab
Target Slab

% Output

Usage (hours)

Time Remaining

Slab

Target Slab

% Output

Usage (hours)

Time Remaining

Slab
Target Slab

% Output

Usage (hours)

Time Remaining

After

power-up,

the control

displays the

“OUTSIDE”

temperature

Press and
release the
item button to
scroll through
the displays
again

POWER-UP DISPLAY

OUTSIDE TEMPERATURE

SLAB TEMPERATURE

Slab

°

F

OUTSIDE

°

F

°

C

OUTSIDE

Slab
Target Slab

% Output

Usage (hours)

Time Remaining

Target Slab

% Output

Usage (hours)

Time Remaining

°

F

TARGET SLAB TEMP.

TIME REMAINING

HOURS OF USE

% HEAT OUTPUT

°

F

Item

Press and

Release the

item button

Item

Press and

Release the

item button

Item

Press and

Release the

item button

Item

Press and

Release the

item button

Item

Press and

Release the

item button

Press and hold

the item button for

at least 1 second

to switch between

°

F and

°

C

Item

Indicator lights

Power light on

The 120 V ac power supply is connected and the control energized.

Remote light on

The remote enable input is

activated.

WWCO light on

The control is in Warm Weather Cut Off.

CWCO light on

The control is in Cold Weather Cut Off.

Melting light on

The system is in Melting Mode.

Idling light on

The system is in Idling Mode.

Water light on

The Snow/Ice Sensor 090 is detecting the presence of water.

Pump light on

The Pump relay is on.

Heat light on

The Heat relay is on.

Test light on

The control is proceeding through the programmed test routine.

Warning light on

The Warning relay is on.

LCD display, indicator lights and Snow/Ice Sensor

When the test button is pressed, the red status lights and LCD segments are
turned on for 7 seconds. The current to the Snow/Ice Sensor’s internal
heater is then increased and if the temperature at the centre of the sensor
does not rise at least 2

°

F in 42 seconds, a warning and error message is

given. If the centre of the sensor is hotter than 120

°

F or the outdoor

temperature is below -5

°

F, the control skips this part of the test. During the

42 seconds the control continues with the remainder of the test sequence.

Warning on

The Warning relay and light turn on and the LCD shows "W A" to indicate that
the Warning device is being tested. If the external warning device does not
activate, the wiring from the control should be checked and the warning
device examined for possible faults. After 10 seconds, the Warning light and
relay are turned off and the test continues.

Note: The test routine can be halted at this, or any of the following steps, by pushing the Test button once. If this is done, the "Test"

light flashes and the control is held in a pause mode for 5 minutes after which time it automatically exits the test routine. Pushing
the Test button during the 5 minute pause allows the control to resume the test routine at the next step.

Pump

Heat

Warning

Power

Remote

Pump

Heat

Warning

CWCO

Melting

Idling

WWCO

Water

Test

°

F

°

C

OUTSIDE

Slab
Target Slab

% Output

Usage (hours)

Time Remaining

• Slab - This is the present surface temperature of the slab as measure by the Snow/Ice Sensor.
• Target Slab - This is the temperature the control wants to achieve i.e. the “Melting” or “Idling” dial setting.
• Time Remaining - When the control is in melting mode and the slab has reached the temperature set by the "Melting" dial, a timer

starts. This display indicates the hours and minutes remaining until the Minimum On Time is reached. The melting system continues
operating after the Minimum On Time is reached if water is still detected.

• Usage - The control displays the total number of hours the heat relay has been on. The upper three digits of the number are displayed

first followed by the lower three digits, followed by a pause.

Example: the control flashes 001 then 298 then pause. The hours of use are therefore 001,298

• % Output - The control varies the amount of heat applied to the snow melt system by cycling the heat relay on and off. This display

indicates the percentage of time the heat relay is on.