Melt 2 The desired slab surface temperature of
zone 2 while in the Melting mode.
Zone 2 = AUTO

32 to 95°F
(0 to 35°C)
Default = 36°F (2°C)

F1

Idle 2 The desired slab surface temperature of
zone 2 while in the Idling Mode.
Zone 2 = AUTO, PRIORITY = NONE

OFF, 20 to 95°F
(OFF, -7 to 35°C)
Default = OFF

Temporary Idle Time for which the temporary
idle is active.

OFF, 0:30 to 40:00 hr
Default = OFF

B

WWSD Warm Weather Shut Down. Slab must
exceed 34°F to enter WWSD.

AUTO, 32 to 95°F
(AUTO, 0 to 36°C)
Default = AUTO

B1

CWCO The Cold Weather Cut Out temperature
for the snow melting system.

OFF, -30 to 50°F
(OFF, -34 to 10°C)
Default = 10°F (-12°C)

E1

Priority Selects priority of zone 1 over zone 2.
ΔT MAX = OFF

NONE, COND, FULL
Default = COND

E1

Priority Selects priority of zone 1 over zone 2.
ΔT MAX ≠ OFF

COND, FULL
Default = COND

A

Mix Maximum The maximum supply water
temperature for the mixing system.

80 to 210°F, OFF
(27 to 99°C, OFF)
Default = 150°F (66°C)

A

Mixing The type of mixing device that is to be used.

FLOT (Floating),
VAR (Variable Speed),
4 – 20 (4-20 mA)
Default = VAR

A

Motor Speed The time the actuating motor
requires to operate from fully closed to fully open.
MIXING = FLOT or MIXING = 4 – 20

30 to 230 seconds
Default = 150 sec

C

Boiler Sensor The location of the boiler sensor.
This affects operation of the Boiler contact.

SUP, RET, NONE
Default = SUP

Item Field

Access
Level

Description

Range

Actual

Setting

Section

LT

D

USER

INS

T

AD

V

664 Adjust Menu (2 of 3)