Dip switches, Dip switch settings, Led status indicators – tekmar 325 Zone Expansion Module User Manual

Page 3: Cleaning the control, Zone group pump, Zone group pump delay, Power led, Zone leds, Zone group pump led

Advertising
background image

3 of 4

© 2005

D 325 - 06/05

DIP Switches

DIP Switch Settings

The DIP switches are found on the left hand side of the 325.

N

Zone Group

89

90

Pmp C

tN4

Meets Class B:
Canadian ICES &
FCC Part 15

5 A (max)

Zone Expansion Module 325

tektra 998-01

Relay Rating: 115 V (ac) 5 A

24 V (ac) Fuse: T2.5 A 250 V

Power

Zone Group Pump C

H7001B

Zone C1

Zone C2

Zone C3

Zone C4

Zone C5

Zone C6

51

52

53

54

55

56

57

58

59

60

61

62

C

C

W

W

R

R

tN4

tN4

C

W

R

tN4

tNt

Zone C1

tNt

Zone C2

tNt

Zone C3

63

64

65

66

67

68

69

70

71

72

73

74

C

C

W

W

R

R

tN4

tN4

C

W

R

tN4

tNt

Zone C4

tNt

Zone C5

tNt

Zone C6

75

76

tN4

C

Zn Grp C

C2
C3

On/Off

Zone Group

Pump C Delay

Zone Group

Pump C

C4
C5
C6

C5
C6
C1

C1

C3

C2

C4

Limited power available, see wiring brochure

77

78

79

80

81

82

83

84

85

86

87

88

Zone C1

Zone C2

Zone C3

Zone C4

Zone C5

Zone C6

C

Vlv

C

Vlv

C

Vlv

C

Vlv

C

Vlv

C

Vlv

Made in Canada

24 V (ac) Fuse: T2.5 A 250 V

C2
C3

On/Off

Zone Group

Pump C Delay

Zone Group

Pump C

C4
C5
C6

C5
C6
C1

C1

C3

C2

C4

Zone Group Pump

Each zone has a corresponding Zone Group Pump DIP
switch.

Zone Group Pump DIP switch set to On:
•

• The Zone Group Pump turns on when the zone calls for

heat.

Zone Group Pump DIP switch set to Off:
•

• The Zone Group Pump does not turn on when the zone

calls for heat.

Zone Group Pump Delay

Each zone has a corresponding Zone Group Pump Delay
DIP switch.

Note: The Zone Group Pump Delay only operates if the
Zone Group Pump DIP switch is set to On.

Zone Group Pump Delay DIP switch set to On:
•

• The Zone Group Pump turns on 3 minutes after the zone

calls for heat

•

• The Zone Group Pump turns off 15 seconds after the

zone stops calling for heat.

Zone Group Pump Delay DIP switch set to Off:
•

• The Zone Group Pump turns on when the zone calls for

heat.

•

• The Zone Group Pump turns off when the zone stops

calling for heat.

LED Status Indicators

Zone Expansion Module 325

Power

Zone Group Pump C

Zone C1

Zone C2

Zone C3

Zone C4

Zone C5

Zone C6

Power LED

Green:
•

• Normal operation.

Amber:
•

• Power is present but the fuse for the internal 24 V (ac)

transformer is blown.

Off:
•

• No power to the Power Input of the Zone Expansion

Module.

Zone LEDs

Green:
•

• The zone is on.

Off:
•

• The zone is off.

Zone Group Pump LED

Green:
•

• The Zone Group Pump relay is on.

Off:
•

• The Zone Group Pump relay is off.

Eight LEDs to provide the status of the 325’s outputs.

Cleaning the Control

The control’s exterior can be cleaned using a damp cloth. Moisten the cloth with water and wring out prior to wiping the
control. Do not use solvents or cleaning solutions.