View Menu (1 of 2)

Item Field

Range

Access

Description

-76 to 149°F

(-60.0 to 65.0°C)

InS

Ad

OUTDOOR

SECTION B

Current outdoor air temperature as measured by the
outdoor sensor.

-22 to 266°F

(-30.0 to 130.0°C)

InS

Ad

MIX 1 SUPPLY

SECTION B

Current Mix 1 supply water temperature as measured
by the Mix 1 supply sensor.

– – –, 35 to 230°F

(– – –, 1.5 to 110.0°C)

Ad

MIX 1 TARGET

SECTION C

The Mix 1 target is the temperature the control
is currently trying to maintain at the Mix 1 supply
sensor. “– – –” is displayed when no heat is required
for Mix 1 zones.

-22 to 266°F

(-30.0 to 130.0°C)

InS

Ad

MIX 2 SUPPLY

SECTION B

Current Mix 2 supply water temperature as measured
by the Mix 2 supply sensor.

Note:

This item is only available when the tN4 DIP

switch is set to Mix 2.

– – –, 35 to 230°F

(– – –, 1.5 to 110.0°C)

Ad

MIX 2 TARGET

SECTION C

The mix 2 target is the temperature the control
is currently trying to maintain at the Mix 2 supply
sensor. “– – –” is displayed when no heat is required
for mix 2 zones.

Note:

This item is only available when the tN4 DIP

switch is set to Mix 2.

-22 to 266°F

(-30.0 to 130.0°C)

InS

Ad

BOILER SUPPLY

SECTION C

Current boiler supply water temperature as measured
by the boiler sensor.

Note:

This item is only available when the Boiler

Sensor Sup / Ret DIP switch is set to Sup.

The View menu items display the current operating
temperatures and status information of the system.

Continued on next page.

VIEW MENU

Display Menus