Exide Technologies GB4013 User Manual

Page 7

Advertising
background image

Page 7

The BWT watering plug assembly – plug, float and gasket (see Figure 1) – is
the heart of the system. It controls the watering of each battery cell to the
recommended shut-off level. This is a minimum of 1/8“ below the vent well at
the end of recharge.

During watering, the rising electrolyte level causes the float to rise. As the
float rises, a self-contained mechanical linkage closes a poppet valve inside
the plug. Once closed, system pressure keeps the valve closed for the
duration of the filling cycle. The installed system is designed to bleed off this
pressure gradually once the quick-disconnect is disconnected.

During watering, the water flows from the filter/regulator unit or tank unit,
through the visual flow indicator (water wheel), quick-disconnect coupler,
in–line filter, and in to the plugs.

SYSTEM REQUIREMENTS

a)

Filtration: The supply water should be filtered to ensure proper long-term operation.
Experience has shown that municipal water supplies typically contain unacceptable amounts of
particles and debris. A 20-micron (or finer) filter is recommended.

NOTE: This is in addition to the auxiliary 100-micron BWT filter pre-
packed with the system.

b)

Pressure: Minimum height of water reservoir must be ten feet.
For municipal water supply lines, a pressure regulator is
required. Recomended static system pressure is 15 psi.
Excessive pressure can cause plugs to snap shut prematurely.
Insufficient pressure will cause the cells to fill more slowly.

c)

Fill Time: The filling system should only be connected long
enough for the cells to fill (usually 1 to 3 minutes). When the flow
indicator stops spinning, the cells are full and the quick-
disconnect should be disconnected.

CAUTION: For systems where a timer control is used, BFS
recommends filling for two minutes.

d)

Float Clearance: Adequate clearance (T1), per Figure 2a/b/c is
required for proper action.

e)

Water Quality: Use only water that meets the following analysis:

Total solids

less than 125 ppm

Fixed solids

less than 75 ppm

Organic and volatile material

less than 50 ppm

Iron

less than 4 ppm

Figure 1

Figure 2a

T1

Figure 2b

T2

Figure 2c

Top of separators

or moss guard

Electrolyte level

clearance

5mm