Exide Technologies SCRFLX Charger User Manual

Page 23

Advertising
background image

Instr. 4770-65-95005-10

Page

19

APPENDIX A: SCRFLX BATTERY CHARGERS. LIST OF DISPLAY INDICATIONS.

Indication

Abbreviation

Interpretation

1.00

1 hour delay set

Delay before charge starts

2.00

2 hour delay set

Delay before charge starts

3.00

3 hour delay set

Delay before charge starts

4.00

4 hour delay set

Delay before charge starts

5.00

5 hour delay set

Delay before charge starts

6.00

6 hour delay set

Delay before charge starts

8.00

8 hour delay set

Delay before charge starts

CHP

CHamPion

Control board is set to 2.55VPC not 2.70VPC.

COL

COoL Down

Charger operates at Cool Down Stage

dEL

dELay

Delay set or Charger operates at Delay Stage

End

End

Charge Cycle complete

FAC or F3

Failure of AC power

Failure of mains

FCA

Failure of DC CAble
disconnection

DC cable disconnected from the battery during the
charge

FCC

or

F2

Failure of Charge Cycle

Battery failed to reach Gassing Voltage (Stage 2)
or
Battery failed to reach End Voltage (Stage 3 of OPC)

FCd

Failure of Cool down

Battery unplugged during Cool Down Stage

FdC

Failure of dC Fuse

Output DC Fuse Failure

FFF

FFatal Failure

Fatal Failure of the charger (Overvoltage or
Overcurrent protection or multifunction of Start Stop
signal)

FOC

Failure of Overall Charge
timer

Overall charge cycle timer protection

FLd

FLooded

Charger set for Flooded batteries

HI

High Voltage Rejection

Battery connected has voltage more than 2.25VPC

LO

LOw Voltage Rejection

Battery connected has voltage less than 1.70VPC

OFF

OFF

Charger is OFF

rEJ

rEJect

Battery connected has voltage too low or too high
or
Battery failed to reach 1.70VPC after 5 min of
charge

rFr

reFreshing Stage

Charger operates at Refreshing Stage

Advertising