11

10. FLX200 STANDARD CHARGER OPERATION

CHARGE CONDITION

DISPLAY

DEFAULT

FUNCTION BUTTON DISPLAY SELECTION

LED

I1

A A,V,Ah,t,Ph

Y*

CONSTANT VOLTAGE

A/ #StSt

A,V,Ah,t,Ph

Y

I2

A A,V,Ah,t,Ph

Y

COOL DOWN PERIOD

CooL / rt

A,V,Ah,t,tr

G*

TERMINATION

rEdy A,V,Ah,t,tr

G

TERMINATION/ FAULT CODE

rEdy / F

A,V,Ah,T,tr

R*, G

REFRESH CHARGE

A / rEFr

A,V,Ah,t,tr

G, Y

SETTING EQUALISE

EqAL

for 5 seconds then default display

Charge

stage

EQUALISE CHARGE

A / EqAL

A,V,Ah,t,tr

G*, Y

AUTO BALANCE

StSt / A StSt / V

A,V,Ah,t,tr

G

Lobt CHARGE PERIOD

Lobt / A

A,V,Ah,t

Y*

Lobt OFF PERIOD

Lobt / V

A,V,Ah,t

CRITICAL FAULT CODE

F

R

NONE CRITICAL FAULT CODE

F

Charge continues

R*

DELAYED START OF CHARGE

dELy / rt

A

= Output current

V

= Volts per cell

Ah

= Returned ampere hours

t

= Time of recharge

F

= Fault code, display will alternate with the two codes

Ph

= Phase of charge i.e. 1, 2 and 3

StSt

= Smart start

Cool

= Cool down period

LoBt

= low battery override

/

= Display will alternate with the two-displayed information

rt

= Remaining time

tr

= Termination method, tr1 = dv/dt, tr2 = I2 entered 3.5 hour timer operated

tr3 = Constant voltage stage entered 3.5 hour timer operated, tr4 = di/dt.
tr5 = Smart Start, tr6 = Autobalance timeout


*
= flashing LED.

NOTE: In LoBt, StSt, Equalise and Termination charge function display will only be displayed for 10 seconds, not
permanently.

# Display if due to smart start.

R: Red

=

Fault, flashing red is a none critical fault.

Y: Yellow

=

Current flowing, flashing yellow when < 2.37VPC.

G: Green

=

charge complete.

Advertising