SCR/SCRF Series Battery Charger

JD5022-00

Preventive Maintenance Procedure

MAINTENANCE DATE

PERFORMED BY

Step (standard features)

Instructions

Results

Clean battery charger

•

All vents clean and open.

•

Remove dust and debris from inside of unit.

¨ OK
¨ OK

Check all electrical
connections and wiring

•

TB1 and TB2 connections all tight.

•

Internal wiring connections tight, slip-on connectors fully seated. Wire
and lug insulation in good condition.

•

Terminations at battery or bus are tight and corrosion free.

¨ OK
¨ OK


¨ OK

Check ac input voltage

•

Measure at TB1-L1, TB1-L2 & TB1-L3 (3 Phase only) using ac
voltmeter. Value must be within +10%, -12% of nominal.

Input

Vac

Check dc output
voltage

•

Measure at TB2(+) and TB2(-) using dc voltmeter. Value should agree
with front panel voltmeter within 2%, and must be correct values for
your battery. If the charger is using a temperature compensation probe,
see the curve in Section VII of user's manual to determine correct
battery voltage.

Float

Vdc

Equalize

Vdc

Check ripple voltage

•

Measure at battery terminals using ac voltmeter set to milliVolts scale.

•

Check against specification listed on charger's Data Nameplate.

Ripple

mVac

Exercise front panel
controls

•

Switch from Float to Equalize, then back to Float.

¨ OK

•

Verify front panel meters functional

¨ Volts OK
¨ Amps OK

•

Verify adjustment capabilities of float and equalize potentiometers.

¨ Float OK
¨ Equalize OK

Check voltage settings

•

Verify voltage setting per battery manufacturer recommendations.

•

Utilize float and equalize potentiometers to make any required
adjustments. See Section IV of user's manual.


¨ Float OK
¨ Equalize OK

Final checks

•

Close and latch front panel door.

•

Restore charger to normal operation.

¨ OK
¨ OK

Step (optional features)

Instructions

Results

Check alarm settings

•

See Section V of SCR/SCRF Series battery charger user’s manual for
calibration of alarms.

¨ HVDC OK
¨ LVDC OK

Combined Alarm Status
Monitor (CASM)

•

See service instruction JD0036-00 for CASM alarm adjustments

•

Test integrity of LEDs by pressing "lamp test" button on front panel.


¨ OK

Check integrity of
remote wiring

•

Internal temperature compensation network wiring. See instruction
JA5022-00 and Section VII of user's manual.

•

Temperature compensation remote probe. See instruction JA5022-00
and Section VII of user's manual.

¨ OK


¨ OK

Step (10-year repair)

Instructions

Results

Replace capacitors

•

See supplied Parts Data Package report or standard replacement parts
table for battery charger manufacturer's part number of optional dc
filtering electrolytic capacitors (C1/C2).

•

Order and replace capacitors

¨ OK