Channel placement, Warning – Amico Equipment Rails User Manual

Page 6

Advertising
background image

5

Amico Accessories Inc.

Channel Placement

1. Before mounting rail at desired height, consider the accessibility to the device controls including the allowable

range of movement of the device when mounted. Built to handle vertical loads up to 60 lbs (27.2155 kg).

2. Devices can only be placed 0.75” (1.905 cm) above the bottom end of the rail because of the rubber stop. Designed

for vertical or horizontal applications.

3. Recommend to allow 14” (35.56 cm) clearance on either side of the rails center line to clear objects such as over-

bed lighting, privacy curtains, adjacent walls or columns, door swing arcs, etc. Power and signal outlets should be

considered when selecting a rail location. Avoid oxygen, vacuum and air outlets, and allow space for attendant

flowmeters and regulators.

WARNING:

The maximum load rating for the Standard Flanged and Flangeless rail is 100 ft-lbs (30.48 m) when

mounted vertically. Refer to qualified personnel. Failure to follow these instructions may result in serious injury.

NOTE:

The rubber stop at the bottom of the rail goes over the shank of the bottom screw. The depressible channel

stop at the top of the rail is used to secure the device, keeping it from sliding up and out of the rail tracks.

Section 3: Installation on Mounting Platform

Drywall

Clearance

Clearance

Bottom of rail

Bottom of device

Top of rail

4”

Mounting height above floor

Floor

Figure 1

Center line

14”

14”

19”

6”

6”

6”

Depressible channel stop.
Depress tab to remove slide/arm
from the wall channel.

Drill hole

Rubber stop

Drill hole

Drill hole

Drill hole

(35.56 cm)

(35.56 cm)

(10.16 cm)

(15.24 cm)

(48.26 cm)

Advertising