6.

All air systems will be equipped with a CO monitor. The monitor will have an alarm to: i) Alarm if the

level of CO exceeds 10 parts per million by volume (ppmv) and ii) Alarm and system shutdown.

A.

Air Compressors

Specifier: select the paragraph below reflecting the preferred technology:

SCROLL COMPRESSORS

1.

The compressors shall be a continuous duty rated scroll type with sealed bearings. The design shall

be single stage, air-cooled, consisting of one fixed and one orbiting scroll sealed with PTFE tip seals

between the scroll halves and rated for 120 PSIG discharge pressure. Orbiting bearings shall be

grease filled and with permanently sealed type requiring no lubrication at any time. Units requiring

re-lubrication are not acceptable. Oil-less type compressor. Noise level shall not exceed 75dB (A) for

duplex system, 77dB (A) for triplex system, and 79 dB (A) for quad system with pumps running at

peak

demand.

2.

On multiple head applications, belt tightening devices are included.

3.

Each compressor shall be equipped with an integral air-cooled after cooler designed for a maximum

approach temperature of 15.0°F complete with electronic drain valve.

4.

The discharge of piping of each compressor shall incorporate an integral valve to prevent more than

1/4 revolution of reverse rotation of the scroll at shutdown.

5.

System piping shall be brazed except where unions are required for service. Vibration flexes shall be

made of metal and of sufficient length to achieve full isolation.

6.

All required Type “K” or “L” copper tubing or brass to interconnect all compressor set components,

with unions for ease of servicing.

7.

The shaft driven radial fan with shroud for air cooling.

8.

Compressor motors shall be a NEMA rated, open drip proof unit with 1.15 service factory suitable for

_____ Volt, _____ Phases, ____Hz.

9.

All moving parts (fans, pulleys and belts) shall be fully protected by an OSHA approved enclosure.

10.

Monitor and numerically display the discharge air temperature at each compression chamber

outlet

port.

11.

Initiate an alarm and shut down the compressor if discharge temperature exceeds the

manufacturer’s recommended level.

RECIPROCATING COMPRESSOR

1.

The compressors shall be single stage, air cooled, and reciprocating type with corrosion resistant valves

with stainless steel reeds. Crankcase ventilation shall be filtered to prevent dust and insects from

entering the crankcase. All bearings shall be permanently lubricated and sealed; compressors that

require bearings to be re-greased are not acceptable.

2.

Each compressor shall be equipped with an integral air-cooled after cooler designed for a

maximum approach temperature of 15.0°F, complete with electronic drain valve.

Advertising